Figure 4-35. programmable functions -42 – Basler Electric DGC-2020 User Manual
Page 152

•
Single-Phase Override (A-C)
G
- The unit switches to single phase A-C sensing configuration even
if the 1 Phase Override Sensing setting is set for A-B. (Note: Applies only when the Single-Phase
Override input is invoked.)
•
Battery Charger Fail
H
- When the selected input is invoked, a user selectable pre-alarm or alarm
is annunciated after the activation delay.
•
Low Coolant Level
I
- When the selected input is invoked, a user selectable pre-alarm or alarm is
annunciated after the activation delay.
•
Fuel Leak Detect
J
- When the selected input is invoked, a user selectable pre-alarm or alarm is
annunciated after the activation delay.
An Alarm Configuration setting of “None” prevents a function from being triggered by a contact input.
Programmable function status is available in BESTlogicPlus Programmable Logic when “None” is
selected.
The BESTCOMSPlus Programmable Functions screen is illustrated in Figure 4-35.
Figure 4-35. Programmable Functions
A
Auto Transfer Switch Input: Select Input (None, 1-16)
B
Grounded Delta Override: Select Input (None, 1-16) and Contact Recognition (Always or While Engine
Running Only).
C
Battle Override: Select Input (None, 1-16) and Contact Recognition (Always or While Engine Running
Only).
D
Low Line Override: Select Input (None, 1-16) and Contact Recognition (Always or While Engine
Running Only).
E
Single Phase Override: Select Input (None, 1-16) and Contact Recognition (Always or While Engine
Running Only).
F
Single Phase Override Sensing: A-B or A-C.
G
Single Phase AC Override: Select Input (None, 1-16) and Contact Recognition (Always or While Engine
Running Only).
H
Battery Charger Fail: Select Input (None, 1-16), Alarm Configuration (None, Alarm, Pre-Alarm),
Activation Delay (s) (0 to 300 s in increments of 1).
I
Low Coolant Level: Select Input (None, 1-16), Alarm Configuration (None, Alarm, Pre-Alarm), Activation
Delay (s) (0 to 300 s in increments of 1).
J
Fuel Leak Detect: Select Input (None, 1-16), Alarm Configuration (None, Alarm, Pre-Alarm), Activation
Delay (s) (0 to 300 s in increments of 1).
4-42
DGC-2020 BESTCOMSPlus
® Software
9400200990 Rev X