Basler Electric DGC-2020 User Manual
Page 237

Name
Description
Symbol
Output Objects
Physical Outputs
OUT1 - OUTx
Physical Outputs 1 through 7 (style xxAxxxxxx) or 1
through 15 (style xxBxxxxxx).
Remote Outputs
OUT13 - OUT36
Remote Outputs 13 through 36.
(Available when an optional CEM-2020 is
connected.)
Alarms
Analog
Expansion
Module
Remote Analog
Inputs 1-8
True when Over 1, Over 2, Under 1, Under 2, or Out
of Range is configured as an alarm and the threshold
has been exceeded. (Over 1 shown.)
Analog
Expansion
Module
Remote Analog
Outputs 1-4
True when the analog output connection is open and
the Out of Range Alarm Configuration is set to
Alarm.
Analog
Expansion
Module
Remote RTD
Inputs 1-8
True when Over 1, Over 2, Under 1, Under 2, or Out
of Range is configured as an alarm and the threshold
has been exceeded. (Over 1 shown.)
Analog
Expansion
Module
Remote
Thermocouple
Inputs 1-2
True when Over 1, Over 2, Under 1, Under 2, or Out
of Range is configured as an alarm and the threshold
has been exceeded. (Over 1 shown.)
Auto Restart Fail
True after the Automatic Restart function fails to
restart the generator.
Battery Charger
Fail
True when the Battery Charger Fail function is
configured as an alarm and the activation delay has
expired.
Configurable
Protection
Protection 1-8
True when Over 1, Over 2, Under 1, or Under 2 is
configured as an alarm and the threshold has been
exceeded. (Over 1 shown.)
Coolant Level
Sender Fail
True when a low coolant level error status code is
received from the ECU. CANBus must be enabled.
Coolant Temp
Sender Fail
True when the Coolant Temp Sender Fail is
configured as an alarm and the activation delay has
expired.
ECU Comm Loss
True when communication to ECU has been lost.
ECU Shutdown
True when ECU has shut down the engine.
Emergency Stop
True when the Emergency Stop button has been
pressed.
Fuel Leak
True when the Fuel Leak Detect function is
configured as an alarm and the activation delay has
expired.
9400200990 Rev X
DGC-2020 BESTlogic
™
Plus Programmable Logic
5-9