Senders, Coolant temperature sender fail configuration type, Coolant temperature sender fail activation delay – Basler Electric DGC-2020 User Manual
Page 449: Oil pressure sender fail configuration type, Oil pressure sender fail activation delay, Fuel level sender fail configuration type, Fuel level sender fail activation delay, Voltage sensing fail configuration type, Voltage sensing fail activation delay
9400200990 Rev X
DGC-2020 Modbus
™ Communication
B-17
Register
Description
Type
Units
Scaling
Factor
R/W
Range
43430
Grounded Delta Override Contact Input
Int32
N/A
N/A
RW
-1 = None
0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
4 = Input 5
5 = Input 6
6 = Input 7
7 = Input 8
8 = Input 9
9 = Input 10
10 = Input 11
11 = Input 12
12 = Input 13
13 = Input 14
14 = Input 15
15 = Input 16
43432
RESERVED
Senders
Register
Description
Type
Units
Scaling
Factor
R/W
Range
43434
Coolant Temperature Sender Fail Configuration
Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
43436
Coolant Temperature Sender Fail Activation Delay
Int32
Minute
N/A
RW
5 - 30
43438
Oil Pressure Sender Fail Configuration Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
43440
Oil Pressure Sender Fail Activation Delay
Int32
Second
N/A
RW
0 - 300
43442
Fuel Level Sender Fail Configuration Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
43444
Fuel Level Sender Fail Activation Delay
Int32
Second
N/A
RW
0 - 300
43446
Voltage Sensing Fail Configuration Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
43448
Voltage Sensing Fail Activation Delay
Int32
Second
N/A
RW
0 - 300
43450
Low Coolant Level Contact Input
Int32
N/A
N/A
RW
-1 = None
0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
4 = Input 5
5 = Input 6
6 = Input 7
7 = Input 8
8 = Input 9
9 = Input 10
10 = Input 11
11 = Input 12
12 = Input 13
13 = Input 14
14 = Input 15
15 = Input 16
43452
Low Coolant Level Config Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
43454
Low Coolant Level Time Delay
Int32
Second
N/A
RW
0 - 300