Table 6-12. RDP-110 Interface Terminals
Terminal
Connects To:
4 (RDP BATT+)
RDP-110 terminal 12/24
5 (RDP BATT–)
RDP-110 terminal DC COM
6 (RDP TXD–)
RDP-110 terminal 485–
7 (RDP TXD+)
RDP-110 485+
Connections for Typical Applications
Connection diagrams for typical applications are shown on the following pages. See Table 6-13 for a
diagram cross-reference.
Table 6-13. Typical Connection Diagram Cross-Reference
Connection Type
Hardware Version 3
Hardware Versions 1 and 2
Three-phase Wye
Figure 6-9, page 6-12
Three-Phase Delta
Single-Phase A-B
Single-Phase A-C
9400200990 Rev X
DGC-2020 Installation
6-11