Generator parameter transmit enable data, Dpf manual regenerate data, Dpf regenerate disable data – Basler Electric DGC-2020 User Manual
Page 490: J1939 speed torque transmit enable data, Engine idle rpm data, Engine parameter transmit enable, Requested mtu smc eng operating mode, Spn conversion method, John deere regeneration interlock, Reserved

B-58
DGC-2020 Modbus
™ Communication
9400200990 Rev X
Register
Description
Type
Units
Scaling
Factor
R/W
Range
45318
Generator Parameter
Transmit Enable Data
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
45320
DPF Manual
Regenerate Data
Int32
N/A
N/A
RW
0 = Off
1 = On
45322
DPF Regenerate
Disable Data
Int32
N/A
N/A
RW
0 = Off
1 = On
45324
J1939 Speed Torque
Transmit Enable Data
Int32
N/A
N/A
RW
0 = Off
1 = On
45326
Engine Idle RPM Data
Int32
N/A
N/A
RW
100 - 2000
45328
Engine Parameter
Transmit Enable
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
45330
Requested MTU SMC
ENG Operating Mode
Int32
N/A
N/A
RW
1 - 2
45332
SPN Conversion
Method
Int32
N/A
N/A
RW
1 - 4
45334
John Deere
Regeneration Interlock
Uint32
N/A
N/A
RW
0 = Disable
1 = Enable
45334-
482
RESERVED
45484
Volt Reg CAN bus
Param Transmit Enable
Data
Int32
N/A
N/A
RW
0 = None
1 = Marathon
2 = Basler
3 = J1939
45486
Volt Reg Primary Volt
Setpoint in DeciVolts
Data
Int32
DeciUnit
Deci
RW
1000 - 6000
45488
Volt Reg Alternate Volt
Setpoint in DeciVolts
Data
Int32
DeciUnit
Deci
RW
1000 - 6000
45490
Volt Reg Volt Adjust
Bandwidth CentiVolts
Data
Int32
CentiUnit
Centi
RW
0 - 3000
45492
Volt Reg Field Current
in Milliamps Data
Int32
MilliUnit
Milli
RW
0 - 30000
45494
Volt Reg Primary UF
Knee in DeciHertz Data
Int32
DeciUnit
Deci
RW
400 - 700
45496
Volt Reg Alternate UF
Knee in DeciHertz Data
Int32
DeciUnit
Deci
RW
400 - 700
45498
Volt Reg Underfreq
Slope in CentiUnits
Int32
CentiUnit
Centi
RW
100 - 500
45500
Analog Input 1 Metering
Value
Int32
CentiUnit
Centi
R
(-100000000) – 99999900
45502
Analog Input 2 Metering
Value
Int32
CentiUnit
Centi
R
(-100000000) – 99999900
45504
Analog Input 3 Metering
Value
Int32
CentiUnit
Centi
R
(-100000000) – 99999900
45506
Analog Input 4 Metering
Value
Int32
CentiUnit
Centi
R
(-100000000) – 99999900
45508
Analog Input 5 Metering
Value
Int32
CentiUnit
Centi
R
(-100000000) – 99999900
45510
Analog Input 6 Metering
Value
Int32
CentiUnit
Centi
R
(-100000000) – 99999900
45512
Analog Input 7 Metering
Value
Int32
CentiUnit
Centi
R
(-100000000) – 99999900
45514
Analog Input 8 Metering
Value
Int32
CentiUnit
Centi
R
(-100000000) – 99999900
45516
RTD Input 1 Metering
Value
Int32
CentiDeg F
Centi
R
(-100000000) – 99999900
45518
RTD Input 2 Metering
Value
Int32
CentiDeg F
Centi
R
(-100000000) – 99999900
45520
RTD Input 3 Metering
Value
Int32
CentiDeg F
Centi
R
(-100000000) – 99999900
45522
RTD Input 4 Metering
Value
Int32
CentiDeg F
Centi
R
(-100000000) – 99999900