Lsm alarm bits, Global alarm, Global pre-alarm – Basler Electric DGC-2020 User Manual
Page 477
9400200990 Rev X
DGC-2020 Modbus
™ Communication
B-45
Register
Description
Type
Units
Scaling
Factor
R/W
Range
44948-49
LSM Alarm Bits
Uint32
N/A
N/A
R
Bit 0 = Not Used
Bit 1 = Not Used
Bit 2 = Not Used
Bit 3 = Not Used
Bit 4 = Not Used
Bit 5 = Not Used
Bit 6 = Not Used
Bit 7 = Not Used
Bit 8 = Not Used
Bit 9 = Not Used
Bit 10 = Not Used
Bit 11 = Not Used
Bit 12 = Not Used
Bit 13 = Not Used
Bit 14 = Not Used
Bit 15 = Not Used
Bit 16 = Not Used
Bit 17 = Not Used
Bit 18 = Not Used
Bit 19 = Not Used
Bit 20 = Not Used
Bit 21 = Not Used
Bit 22 = Not Used
Bit 23 = Not Used
Bit 24 = Not Used
Bit 25 = Duplicate LSM
Bit 26 = ID Repeat
Bit 27 = ID Missing
Bit 28 = LSM Comms Failure
Bit 29 = Intergenset Comms Failure
Bit 30 = GOV Output Limit
Bit 31 = AVR Output Limit
44950
Global Alarm
Uint32
N/A
N/A
R
Bit 0 = No system alarms in effect
Bit 1 = System alarm(s) in effect
44952
Global Pre-Alarm
Uint32
N/A
N/A
R
Bit 0 = No system pre-alarms in
effect
Bit 1 = System pre-alarm(s) in
effect