beautypg.com

Basler Electric DGC-2020 User Manual

Page 526

background image

B-94

DGC-2020 Modbus

™ Communication

9400200990 Rev X

Register

Description

Type

Units

Scaling

Factor

R/W

Range

45960

Conf Prot 8 Threshold 2
Activation Delay

Int32

Second

N/A

RW

0 - 300

45962

Conf Prot 8 Over 1
Threshold

Int32

N/A

Centi

RW

(-99999900) - 99999900

45964

Conf Prot 8 Over 2
Threshold

Int32

N/A

Centi

RW

(-99999900) - 99999900

45966

Conf Prot 8 Under 1
Threshold

Int32

N/A

Centi

RW

(-99999900) - 99999900

45968

Conf Prot 8 Under 2
Threshold

Int32

N/A

Centi

RW

(-99999900) - 99999900

45970

Conf Prot 8 Over 1
Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only

45972

Conf Prot 8 Over 2
Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only

45974

Conf Prot 8 Under 1
Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only

45976

Conf Prot 8 Under 2
Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only

45978-
999

FUTURE USE

46000

J1939-Transmission Oil
Pressure

Uint32

16 kPa/bit, 0 offset

N/A

R

0 to +4000 kPa (0 to 580 psi)

46002

J1939-Transmission Oil
Temp

Uint32

.03125 Deg C/bit
Offset -273 Deg C

N/A

R

−273 to +1735.0 °C

(−459.4 to 3155.0 °F)

46004

J1939-Winding 1 Temp

Uint32

1 Deg C Per Bit
Offset -40 Deg C

N/A

R

−40 to +210 °C (−40 to 410 °F)

46006

J1939-Winding 2 Temp

Uint32

1 Deg C Per Bit
Offset -40 Deg C

N/A

R

−40 to +210 °C (−40 to 410 °F)

46008

J1939-Winding 3 Temp

Uint32

1 Deg C Per Bit
Offset -40 Deg C

N/A

R

−40 to +210 °C (−40 to 410 °F)

46010

J1939-ECU Temp

Uint32

.03125 Deg C/bit
Offset -273 Deg C

N/A

R

-273 to 1734.96875 degC

46012

J1939-Aux Pressure 1

Uint32

16 kPa/bit 0 Offset

N/A

R

0 to 4000 kPa

46014

J1939-Aux Pressure 2

Uint32

16 kPa/bit 0 Offset

N/A

R

0 to 4000 kPa

46016

J1939-Rated Power

Uint32

0.5 kW/bit 0 Offset

N/A

R

0 to 32,127.5 kW

46018

J1939-Rated RPM

Uint32

0.125 rpm/bit 0
Offset

N/A

R

0 to 8,031.875 rpm

46020

J1939-Exhaust Temp A

Uint32

.03125 Deg C/bit
Offset -273 Deg C

N/A

R

-273 to 1734.96875 degC

46022

J1939-Exhaust Temp B

Uint32

.03125 Deg C/bit
Offset -273 Deg C

N/A

R

-273 to 1734.96875 degC

46024

J1939-Charge Air Temp

Uint32

.03125 Deg C/bit
Offset -273 Deg C

N/A

R

-273 to 1734.96875 degC

46026

J1939-ADEC ECU Error
Code

Uint32

No Scale or Offset

N/A

R

0 - 65535

46028

J1939-ADEC Selected
Speed Demand

Uint32

0.125 rpm/bit, 0 rpm
offset

N/A

R

0 - 8031.875

46030

J1939-ADEC Effective
Set Speed

Uint32

0.125 rpm/bit, 0 rpm
offset

N/A

R

0 - 8031.875

This manual is related to the following products: