1 phase overvoltage activation delay (59-1), 1 phase overvoltage alarm configuration (59-1), Underfrequency pickup – Basler Electric DGC-2020 User Manual

Page 460: Underfrequency activation delay, Underfrequency inhibit voltage, Underfrequency alarm configuration, Overfrequency pickup, Overfrequency activation delay, Overfrequency alarm configuration, 3 phase overcurrent pickup(51-2)

background image

B-28

DGC-2020 Modbus

™ Communication

9400200990 Rev X

Register

Description

Type

Units

Scaling

Factor

R/W

Range

44296

1 Phase Overvoltage Activation
Delay (59-1)

Uint32

Decisecond

Deci

RW

0 - 300

44298

1 Phase Overvoltage Alarm
Configuration (59-1)

Uint32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only

44300

Underfrequency Pickup

Uint32

DeciHertz

Deci

RW

450 - 4400

44302

Underfrequency Activation Delay

Uint32

Decisecond

Deci

RW

0 - 300

44304

Underfrequency Inhibit Voltage

Uint32

Volt

N/A

RW

70 - 576

44306

Underfrequency Alarm
Configuration

Uint32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only

44308

Overfrequency Pickup

Uint32

DeciHertz

Deci

RW

450 - 4400

44310

Overfrequency Activation Delay

Uint32

Decisecond

Deci

RW

0 - 300

44312

Overfrequency Alarm
Configuration

Uint32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only

44314

Overcurrent Low Line Scale
Factor (51-1)

Float

N/A

N/A

RW

0.001 - 3

44316

Overvoltage Low Line Scale
Factor (59-1)

Float

N/A

N/A

RW

0.001 - 3

44318

Undervoltage Low Line Scale
Factor (27-1)

Float

N/A

N/A

RW

0.001 - 3

44320

3 Phase Overcurrent Pickup
(51-2)

Uint32

CentiAmp

Centi

RW

18 - 775

44322

3 Phase Overcurrent Time Dial
(51-2)

Uint32

DeciUnit

Deci

RW

0 - 72000

44324

3 Phase Overcurrent Curve
(51-2)

Uint32

N/A

N/A

RW

0 = S1 Curve
1 = S2 Curve
2 = L1 Curve
3 = L2 Curve
4 = D Curve
5 = M Curve
6 = I1 Curve
7 = I2 Curve
8 = V1 Curve
9 = V2 Curve
10 = E1 Curve
11 = E2 Curve
12 = A Curve
13 = B Curve
14 = C Curve
15 = G Curve
16 = F Curve
17 = Programmable

44326

3 Phase Overcurrent Alarm
Configuration (51-2)

Uint32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only

44328

1 Phase Overcurrent Pickup
(51-2)

Uint32

CentiAmp

Centi

RW

18 - 775

44330

1 Phase Overcurrent Time Dial
(51-2)

Uint32

DeciUnit

Deci

RW

0 - 72000