Ecu setup, Ecu setup -22, Figure 4-19. canbus setup -22 – Basler Electric DGC-2020 User Manual
Page 132: Table 4-5. generator parameter transmit -22, The dgc-2020 solution

Not being able to stop the engine without removing ECU power causes two problems. The first problem is
that the only way to stop the engine is to turn the ECU off and wait for the engine speed to decrease
below 60 rpm before powering the ECU back on. Otherwise, the engine will take off running. The second
problem is that while the ECU is off, you can no longer meter and update coolant level, coolant
temperature alarm/pre-alarm, and crank control.
The DGC-2020 Solution
The DGC-2020 resolves ECU limitations by using four timers:
•
Engine Shutdown.
G
The time in seconds to stay disconnected from the ECU when going from
running to shutdown before starting the first pulse. This timer should allow enough time for the
engine to slow down so that when the DGC-2020 pulses, the ECU will not start the engine.
•
Pulse Cycle Time.
H
The time in minutes that the controller waits before pulsing.
•
Settling Time.
I
The time in tenths of seconds to gather data after connecting to the ECU during
the pulsing state. This allows all the metered values to be sent and ramp as designated by the
J1939 protocol. ECU values initially sent are low and the ECU takes time to average out its own
data values.
•
Response Timeout.
J
The time in seconds to attempt communication with the ECU when the DGC-
2020 is in the pulsing state or connecting state.
Figure 4-19. CAN Bus Setup
A
Enable ECU Support: Check box to enable ECU support.
B
Enable DTC Support: Check box to enable DTC support.
C
SPN Conversion Method: 1, 2, 3, or 4.
D
CAN bus Address: Accepts an address number from 1 to 253 in increments of 1.
E
Output Select: Fuel Contact (RUN) or Pre-start Contact.
F
Pulsing: Enable or Disable.
G
Engine Shutdown: Adjustable from 1 to 60 s in 1 s increments.
H
Pulse Cycle Time: Adjustable from 1 to 60 min in 1 min increments.
I
Settling Time: Adjustable from 5,500 to 30,000 ms in 1 ms increments.
J
Response Timeout: Adjustable from 1 to 60 s in 1 s increments.
ECU Setup
The DGC-2020 can be configured for Standard, Volvo Penta, MTU MDEC, MTU ADEC, MTU
ECU7/ECU8, GM/Doosan, Cummins, MTU Smart Connect, Scania, or John Deere
A
. When the Generator
Parameter Transmit
B
setting is enabled, the DGC-2020 broadcasts generator metered parameters over
CANBus as listed in Table 4-5. The Generator Parameter Transmit setting is not used when ECU Type is
set for MTU MDEC, MTU ECU7/ECU8, or MTU Smart Connect.
Table 4-5. Generator Parameter Transmit
PGN Name
PGN
(Hex)
SPN
Parameter
Units
Scaling /
Offset
Bytes
Within
PGN
Data
Generator
Total AC
Energy
65018
(FDFA)
2468
Generator Total kW Hours Export
kWh
n/a
1 to 4
2469
Generator Total kW Hours Import
kWh
n/a
5 to 8
4-22
DGC-2020 BESTCOMSPlus
® Software
9400200990 Rev X