Register

Description

Type

Units

Scaling

Factor

R/W

Range

46802

User Config Input 9
Engine Running Only

Int32

N/A

N/A

RW

0 = Always
1 = While Engine Running Only

46804

User Config Input 10
Config Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm

46806

User Config Input 10
Time Delay

Int32

Second

N/A

RW

0 – 300

46808

User Config Input 10
Engine Running Only

Int32

N/A

N/A

RW

0 = Always
1 = While Engine Running Only

46810

User Config Input 11
Config Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm

46812

User Config Input 11
Time Delay

Int32

Second

N/A

RW

0 – 300

46814

User Config Input 11
Engine Running Only

Int32

N/A

N/A

RW

0 = Always
1 = While Engine Running Only

46816

User Config Input 12
Config Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm

46818

User Config Input 12
Time Delay

Int32

Second

N/A

RW

0 – 300

46820

User Config Input 12
Engine Running Only

Int32

N/A

N/A

RW

0 = Always
1 = While Engine Running Only

46822

User Config Input 13
Config Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm

46824

User Config Input 13
Time Delay

Int32

Second

N/A

RW

0 – 300

46826

User Config Input 13
Engine Running Only

Int32

N/A

N/A

RW

0 = Always
1 = While Engine Running Only

46828

User Config Input 14
Config Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm

46830

User Config Input 14
Time Delay

Int32

Second

N/A

RW

0 – 300

46832

User Config Input 14
Engine Running Only

Int32

N/A

N/A

RW

0 = Always
1 = While Engine Running Only

46834

User Config Input 15
Config Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm

46836

User Config Input 15
Time Delay

Int32

Second

N/A

RW

0 – 300

46838

User Config Input 15
Engine Running Only

Int32

N/A

N/A

RW

0 = Always
1 = While Engine Running Only

46840

User Config Input 16
Config Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm

46842

User Config Input 16
Time Delay

Int32

Second

N/A

RW

0 – 300

46844

User Config Input 16
Engine Running Only

Int32

N/A

N/A

RW

0 = Always
1 = While Engine Running Only

46846

User Config Input 17
Config Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm

46848

User Config Input 17
Time Delay

Int32

Second

N/A

RW

0 – 300

46850

User Config Input 17
Engine Running Only

Int32

N/A

N/A

RW

0 = Always
1 = While Engine Running Only

46852

User Config Input 18
Config Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm

46854

User Config Input 18
Time Delay

Int32

Second

N/A

RW

0 – 300