Basler Electric DGC-2020 User Manual
Page 574

B-142
DGC-2020 Modbus
™ Communication
9400200990 Rev X
Holding
Register
Parameter
Range
Read/Write
Supported
Data
Format
Units
40376
Active Speed Signal Sources
1-4
R -
1 =MPU
2 =ALT
3 =GEN
4 =NONE
40377
Sender Failure Alarm Codes
R -
b0=Cool Temp
b1=Oil Press
b2 Reserved
b3=Spd Signal
b4=Gen Volt
b5-b7 Not Used
40378
Alarm Codes
R -
b0=Hi Cool
Temp
b1 Low Coolant
Level
b2=Airbox
b3=E-Stop
b4=Sender Fail
b5=Over-crank
b6=Over-speed
b7=Low Oil
Press
40379
Pre-Alarm Codes
R -
b0=Hi Cool
Temp
b1=Low Cool
Temp
b2=Weak Batt
b3=Low Batt
b4 =Batt ov
b5=Charger Fail
b6=Service Due
b7=kW Overload
40380
Pre-Alarm Codes, Group 2
R -
b0=Low Oil
Press
b1=Low Fuel
b2 Reserved
b3 Reserved
b4-b7 Not Used
40381
Engine Coolant Temperature
R -
DegF
40382
Engine Oil Pressure
R -
PSI
40383
Battery Voltage
R -
.1 VoltDC
40384
Fuel Level
R -
% Full Tank
40385
Time Remaining until
Maintenance
R -
Hours
40386
Accumulated Engine Runtime(a)
R -
DP
Minutes x 10000
40387
Accumulated Engine Runtime(b)
R -
DP
Minutes
40388
Accumulated Engine Runtime
Warranty(a)
R W
DP
Minutes x 10000
40389
Accumulated Engine Runtime
Warranty(b)
R W
DP
Minutes
40390
Engine Speed(a)
R -
DP
RPM x 10000
40391
Engine Speed(b)
R -
DP
RPM
40392
Engine Load(a)
R -
DP
%
40393
Engine Load(b)
R -
DP
%
GENERATOR MONITOR
40394
Phase a-b RMS Voltage(a)
R -
DP
RMS Volt x10000
40395
Phase a-b RMS Voltage(b)
R -
DP
RMS Volt
40396
Phase b-c RMS Voltage(a)
R -
DP
RMS Volt x10000
40397
Phase b-c RMS Voltage(b)
R -
DP
RMS Volt
40398
Phase c-a RMS Voltage(a)
R -
DP
RMS Volt x10000
40399
Phase c-a RMS Voltage(b)
R -
DP
RMS Volt
40400
Phase a-n RMS Voltage(a)
R -
DP
RMS Volt x10000
40401
Phase a-n RMS Voltage(b)
R -
DP
RMS Volt
40402
Phase b-n RMS Voltage(a)
R -
DP
RMS Volt x10000