Programmable Curves for Overcurrent Protection

Inverse overcurrent characteristics for trip and reset programmable curves are defined by Equation 4-1
and 4-2 respectively. These equations comply with IEEE Std C37.112-1996 - IEEE Standard Inverse-
Time Characteristic Equations for Overcurrent Relays
. The curve-specific coefficients are defined for the
standard curves as listed in Appendix A, Time Overcurrent Characteristic Curves. When inverse time
overcurrent characteristic curve P is selected, the coefficients used in the equation are those defined by
the user. Definitions for these equations are provided in Table 4-6.

Equation 4-1. Time OC Characteristics for Trip

(

)

K

BD

C

M

AD

T

Q

N

T

+

+

=

Equation 4-2. Time OC Characteristics for Reset

|

1

M

|

RD

T

2

R

=

Table 4-6. Definitions for Equations 4-1 and 4-2

Parameter

Description

Explanation

T

T

Time to trip

Time that the 51-x function will take to time out and trip.

D

Time dial setting

Time dial setting for the 51-x function.

M

Multiple of pickup

Measured current in multiples of pickup. The timing
algorithm has a dynamic range of 0 to 40 times pickup.

A

Coefficient specific to
selected curve

Affects the effective range of the time dial.

B

Coefficient specific to
selected curve

Affects a constant term in the timing equation. Has greatest
effect on curve shape at high multiples of pickup.

C

Coefficient specific to
selected curve

Affects the multiple of pickup where the curve would
approach infinity if allowed to continue below pickup. Has
greatest effect on curve shape near pickup.

N

Multiple of Pickup
exponent specific to
selected curve

Affects how inverse the characteristics are. Has greatest
effect on curve shape at low to medium multiples of pickup.

K

Constant

Characteristic minimum delay term. Fixed at 0.028.

T

R

Time to reset

Relevant if 51-x function is set for integrating reset.

R

Coefficient specific to
selected curve

Affects the speed of reset when integrating reset is selected.

Q

Denominator exponent
specific to selected curve.

Affects how inverse the characteristics are. Has greater
affect as Q is increased.

Setting Programmable (P) Curves

Curve coefficients

J

are entered using BESTCOMSPlus. Table 4-7 lists the programmable curve settings.

Table 4-7. Programmable Time Current Characteristic Curve Coefficients

Setting

Range

Increment

Default

A Coefficient

0 to 600

0.0001

0.2663

B Coefficient

0 to 25

0.0001

0.0339

C Coefficient

0 to 1

0.0001

1.0000

N Coefficient

0.5 to 2.5

0.0001

1.2969

Q Coefficient

0.1 to 10

0.0001

1.0000

R Coefficient

0 to 30

0.0001

0.5000

4-68

DGC-2020 BESTCOMSPlus

® Software

9400200990 Rev X