Basler Electric DGC-2020 User Manual

Page 530

background image

B-98

DGC-2020 Modbus

™ Communication

9400200990 Rev X

Register

Description

Type

Units

Scaling

Factor

R/W

Range

46344

AEM Input 1 Under 2
Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only

46346

AEM Input 1 Out of
Range Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only

46348

AEM Input 2 Max
Voltage

Int32

DeciVolt

Deci

RW

0 - 100

46350

AEM Input 2 Max
Current

Int32

Milliamp x 10

Deci

RW

40 - 200

46352

AEM Input 2 Min
Voltage

Int32

DeciVolt

Deci

RW

0 - 100

46354

AEM Input 2 Min
Current

Int32

Milliamp x 10

Deci

RW

40 - 200

46356

AEM Input 2 Param Max

Int32

Centi Unit

Centi

RW

(-100000000) – 99999900

46358

AEM Input 2 Param Min

Int32

Centi Unit

Centi

RW

(-100000000) – 99999900

46360

AEM Input 2 Hysteresis

Int32

Deci Percent

Deci

RW

0 – 1000

46362

AEM Input 2 Arming
Delay

Int32

Second

N/A

RW

0 – 300

46364

AEM Input 2 Threshold
1 Activation Delay

Int32

Second

N/A

RW

0 – 300

46366

AEM Input 2 Threshold
2 Activation Delay

Int32

Second

N/A

RW

0 – 300

46368

AEM Input 2 Over 1
Threshold

Int32

Centi Unit

Centi

RW

(-100000000) – 99999900

46370

AEM Input 2Over 2
Threshold

Int32

Centi Unit

Centi

RW

(-100000000) – 99999900

46372

AEM Input 2 Under 1
Threshold

Int32

Centi Unit

Centi

RW

(-100000000) – 99999900

46374

AEM Input 2Under 2
Threshold

Int32

Centi Unit

Centi

RW

(-100000000) – 99999900

46376

AEM Input 2 Over 1
Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only

46378

AEM Input 2 Over 2
Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only

46380

AEM Input 2 Under 1
Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only

46382

AEM Input 2 Under 2
Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only

46384

AEM Input 2 Out of
Range Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only

46386

AEM Input 3 Max
Voltage

Int32

DeciVolt

Deci

RW

0 - 100

46388

AEM Input 3 Max
Current

Int32

Milliamp x 10

Deci

RW

40 - 200

46390

AEM Input 3 Min
Voltage

Int32

DeciVolt

Deci

RW

0 - 100

46392

AEM Input 3 Min
Current

Int32

Milliamp x 10

Deci

RW

40 - 200

46394

AEM Input 3 Param Max

Int32

Centi Unit

Centi

RW

(-100000000) – 99999900

46396

AEM Input 3 Param Min

Int32

Centi Unit

Centi

RW

(-100000000) – 99999900

46398

AEM Input 3 Hysteresis

Int32

Deci Percent

Deci

RW

0 – 1000