Legacy parameter table for dgc-500 and dgc-1000 – Basler Electric DGC-2020 User Manual
Page 554
B-122
DGC-2020 Modbus
™ Communication
9400200990 Rev X
Register
Description
Type
Units
Scaling
Factor
R/W
Range
47272
AEM1 Thermocouple1
Under 2 Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
47274
AEM1 Thermocouple1
Out of Range Alarm
Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
47276
AEM1 Thermocouple2
Hysteresis
Int32
DeciPercent
Deci
RW
0 - 1000
47278
AEM1 Thermocouple2
Arming Delay
Int32
Second
N/A
RW
0 - 300
47280
AEM1 Thermocouple2
Threshold1 Activation
Delay
Int32
Second
N/A
RW
0 - 300
47282
AEM1 Thermocouple2
Threshold2 Activation
Delay
Int32
Second
N/A
RW
0 - 300
47284
AEM1 Thermocouple2
Over1 Threshold
Int32
Deg F
N/A
RW
32 - 2507
47286
AEM1 Thermocouple2
Over2 Threshold
Int32
Deg F
N/A
RW
32 - 2507
47288
AEM1 Thermocouple2
Under1 Threshold
Int32
Deg F
N/A
RW
32 - 2507
47290
AEM1 Thermocouple2
Under2 Threshold
Int32
Deg F
N/A
RW
32 - 2507
47292
AEM1 Thermocouple2
Over1 Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
47294
AEM1 Thermocouple2
Over2 Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
47296
AEM1 Thermocouple2
Under1 Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
47298
AEM1 Thermocouple2
Under 2 Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
47300
AEM1 Thermocouple2
Out of Range Alarm
Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
Legacy Parameter Table for DGC-500 and DGC-1000
The DGC-2020 maps all legacy parameters previously associated with the DGC-500 and DGC-1000 into
the Holding Register address space (40000 to 41999). Query address N will access the Holding Register
N+1. The Data Format is Integer type data unless identified otherwise in the Data Format column.
Holding
Register
Parameter
Range
Read/Write
Supported
Data
Format
Units
40001-18
RESERVED
PARAMETER SETTINGS
40019
Emergency Stop
0-1
R W
0 =Off
1 =Stop
40020
Remote Start / Stop: Runs when in
Auto mode
0-1
R W
0 =Stop
1 =Start
40021-22
RESERVED