Basler Electric DGC-2020 User Manual
Page 242
Name
Description
Symbol
Engine kW Over
Load 3
True when the Engine kW Overload 3 Pre-Alarm
settings have been exceeded.
Fuel Leak
True when the Fuel Leak Detect function is
configured as a pre-alarm and the activation delay
has expired.
Fuel Level
Sender Fail
True when the Fuel Level Sender Fail is configured
as a pre-alarm and the activation delay has expired.
Generator
Breaker Close
Fail
True when a generator breaker close fail pre-alarm
occurs. The pre-alarm occurs when the DGC-2020
has issued a generator breaker close output but
does not receive a generator breaker status input
that indicates the breaker has closed before the
breaker close wait time has expired.
Generator
Breaker Open
Fail
True when a generator breaker open fail pre-alarm
occurs. The pre-alarm occurs when the DGC-2020
has issued a generator breaker open output but does
not receive a generator breaker status input that
indicates the breaker has opened before the breaker
close wait time has expired.
Generator
Breaker Sync
Fail
True when a generator breaker sync fail pre-alarm
occurs. The pre-alarm occurs when the synchronizer
is running and attempting to close the generator
breaker but the sync fail activation delay expires prior
to achieving breaker closure.
Generator
Protection
27-1
True when the 27-1 element is configured as a pre-
alarm and has tripped.
Generator
Protection
27-2
True when the 27-2 element is configured as a pre-
alarm and has tripped.
Generator
Protection
59-1
True when the 59-1 element is configured as a pre-
alarm and has tripped.
Generator
Protection
59-2
True when the 59-2 element is configured as a pre-
alarm and has tripped.
Generator
Protection
32
True when the 32 element is configured as a pre-
alarm and has tripped.
Generator
Protection
40
True when the 40 element is configured as a pre-
alarm and has tripped.
Generator
Protection
47
True when the 47 element is configured as a pre-
alarm and has tripped.
Generator
Protection
51-1
True when the 51-1 element is configured as a pre-
alarm and has tripped.
Generator
Protection
51-2
True when the 51-2 element is configured as a pre-
alarm and has tripped.
5-14
DGC-2020 BESTlogic
™
Plus Programmable Logic
9400200990 Rev X