Basler Electric DGC-2020 User Manual

Page 529

background image

9400200990 Rev X

DGC-2020 Modbus

™ Communication

B-97

Register

Description

Type

Units

Scaling

Factor

R/W

Range

46262

PLC Timer 7 Seconds

Int32

Second

Deci

RW

0 - 18000

46264

PLC Timer 8 Seconds

Int32

Second

Deci

RW

0 - 18000

46266

PLC Timer 9 Seconds

Int32

Second

Deci

RW

0 - 18000

46268

PLC Timer 10 Seconds

Int32

Second

Deci

RW

0 - 18000

46270

PLC Timer 1 Minutes

Uint32

Minute

N/A

RW

0 - 250

46272

PLC Timer 2 Minutes

Uint32

Minute

N/A

RW

0 - 250

46274

PLC Timer 3 Minutes

Uint32

Minute

N/A

RW

0 - 250

46276

PLC Timer 4 Minutes

Uint32

Minute

N/A

RW

0 - 250

46278

PLC Timer 5 Minutes

Uint32

Minute

N/A

RW

0 - 250

46280

PLC Timer 6 Minutes

Uint32

Minute

N/A

RW

0 - 250

46282

PLC Timer 7 Minutes

Uint32

Minute

N/A

RW

0 - 250

46284

PLC Timer 8 Minutes

Uint32

Minute

N/A

RW

0 - 250

46286

PLC Timer 9 Minutes

Uint32

Minute

N/A

RW

0 - 250

46288

PLC Timer 10 Minutes

Uint32

Minute

N/A

RW

0 - 250

46290

PLC Timer 1 Hours

Uint32

Hour

N/A

RW

0 - 250

46292

PLC Timer 2 Hours

Uint32

Hour

N/A

RW

0 - 250

46294

PLC Timer 3 Hours

Uint32

Hour

N/A

RW

0 - 250

46296

PLC Timer 4 Hours

Uint32

Hour

N/A

RW

0 - 250

46298

PLC Timer 5 Hours

Uint32

Hour

N/A

RW

0 - 250

46300

PLC Timer 6 Hours

Uint32

Hour

N/A

RW

0 - 250

46302

PLC Timer 7 Hours

Uint32

Hour

N/A

RW

0 - 250

46304

PLC Timer 8 Hours

Uint32

Hour

N/A

RW

0 - 250

46306

PLC Timer 9 Hours

Uint32

Hour

N/A

RW

0 - 250

46308

PLC Timer 10 Hours

Uint32

Hour

N/A

RW

0 - 250

46310

AEM Input 1 Max
Voltage

Int32

DeciVolt

Deci

RW

0 - 100

46312

AEM Input 1 Max
Current

Int32

Milliamp x 10

Deci

RW

40 - 200

46314

AEM Input 1 Min
Voltage

Int32

DeciVolt

Deci

RW

0 - 100

46316

AEM Input 1 Min
Current

Int32

Milliamp x 10

Deci

RW

40 - 200

46318

AEM Input 1 Param Max

Int32

Centi Unit

Centi

RW

(-100000000) – 99999900

46320

AEM Input 1 Param Min

Int32

Centi Unit

Centi

RW

(-100000000) – 99999900

46322

AEM Input 1 Hysteresis

Int32

Deci Percent

Deci

RW

0 – 1000

46324

AEM Input 1 Arming
Delay

Int32

Second

N/A

RW

0 – 300

46326

AEM Input 1 Threshold
1 Activation Delay

Int32

Second

N/A

RW

0 – 300

46328

AEM Input 1 Threshold
2 Activation Delay

Int32

Second

N/A

RW

0 – 300

46330

AEM Input 1 Over 1
Threshold

Int32

Centi Unit

Centi

RW

(-100000000) – 99999900

46332

AEM Input 1Over 2
Threshold

Int32

Centi Unit

Centi

RW

(-100000000) – 99999900

46334

AEM Input 1 Under 1
Threshold

Int32

Centi Unit

Centi

RW

(-100000000) – 99999900

46336

AEM Input 1Under 2
Threshold

Int32

Centi Unit

Centi

RW

(-100000000) – 99999900

46338

AEM Input 1 Over 1
Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only

46340

AEM Input 1 Over 2
Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only

46342

AEM Input 1 Under 1
Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only