Basler Electric DGC-2020 User Manual
Page 570
B-138
DGC-2020 Modbus
™ Communication
9400200990 Rev X
Holding
Register
Parameter
Range
Read/Write
Supported
Data
Format
Units
40114
Alternator Frequency Rated
Maximum
900
R -
Hertz
40115
Alternator Frequency Rated
Stepsize
1
R -
Hertz
GENERATOR PT PRIMARY
40121
Voltage(a)
1-15000
R W
DP
VoltsAC x 10000
40122
Voltage(b)
R W
DP
VoltsAC
40123
Voltage Minimum(a)
1
R -
DP
VoltsAC x 10000
40124
Voltage Minimum(b)
R -
DP
VoltsAC
40125
Voltage Maximum(a)
15000
R -
DP
VoltsAC x 10000
40126
Voltage Maximum(b)
R -
DP
VoltsAC
40127
Voltage Stepsize(a)
1
R -
DP
VoltsAC x 10000
40128
Voltage Stepsize(b)
R -
DP
VoltsAC
GENERATOR PT SECONDARY
40129
Voltage
1-480
R W
VoltsAC
40130
Voltage Minimum
1
R -
VoltsAC
40131
Voltage Maximum
480
R -
VoltsAC
40132
Voltage Stepsize
1
R -
VoltsAC
GENERATOR CT PRIMARY
40133
Current
1-5000
R W
AmpsAC
40134
Current Minimum
1
R -
AmpsAC
40135
Current Maximum
5000
R -
AmpsAC
40136
Current Stepsize
1
R -
AmpsAC
BUS PT PRIMARY
40141
Voltage(a)
1-15000
R W
DP
VoltsAC x 10000
40142
Voltage(b)
R W
DP
VoltsAC
40143
Voltage Minimum(a)
1
R -
DP
VoltsAC x 10000
40144
Voltage Minimum(b)
R -
DP
VoltsAC
40145
Voltage Maximum(a)
15000
R -
DP
VoltsAC x 10000
40146
Voltage Maximum(b)
R -
DP
VoltsAC
40147
Voltage Stepsize(a)
1
R -
DP
VoltsAC x 10000
40148
Voltage Stepsize(b)
R -
DP
VoltsAC
BUS PT SECONDARY
40149
Voltage
1-480
R W
VoltsAC
40150
Voltage Minimum
1
R -
VoltsAC
40151
Voltage Maximum
480
R -
VoltsAC
40152
Voltage Stepsize
1
R -
VoltsAC
LOW FUEL PRE-ALARM
40181
Enable
0-1
R W
0 =Off
1 =On
40182
Threshold
10-100
R W
% Full Tank
40183
Minimum
10
R -
% Full Tank
40184
Maximum
100
R -
% Full Tank
40185
Stepsize
1
R -
% Full Tank
LOW COOL TEMP PRE-ALARM
40186
Enable
0-1
R W
0 =Off
1 =On