Basler Electric DGC-2020 User Manual
Page 539
![background image](https://www.manualsdir.com/files/773941/content/doc539.png)
9400200990 Rev X
DGC-2020 Modbus
™ Communication
B-107
Register
Description
Type
Units
Scaling
Factor
R/W
Range
46688
AEM Output 3 Max
Voltage
Int32
DeciVolt
Deci
RW
0 – 100
46690
AEM Output 3 Max
Current
Int32
Milliamp x 10
Deci
RW
40 – 200
46692
AEM Output 3 Min
Voltage
Int32
DeciVolt
Deci
RW
0 – 100
46694
AEM Output 3 Min
Current
Int32
Milliamp x 10
Deci
RW
40 – 200
46696
AEM Output 3 Param
Max
Int32
Centi Unit
Centi
RW
(-100000000) – 99999900
46698
AEM Output 3 Param
Min
Int32
Centi Unit
Centi
RW
(-100000000) – 99999900
This manual is related to the following products: