Basler Electric DGC-2020 User Manual
Page 339

iii. Min Output Current (mA) - This setting defines the minimum AVR bias current level if
the bias Output Type is set to Current.
iv. Max Output Current (mA) - This setting defines the maximum AVR bias current level
if the bias Output Type is set to Current.
v. Min Output Voltage (V) - This setting defines the minimum AVR bias voltage level if
the bias Output Type is set to Voltage.
vi. Max Output Voltage (V) - This setting defines the maximum AVR bias voltage level if
the bias Output Type is set to Voltage.
d. Configure the governor bias output voltage or current range and polarity.
Before this can be done, the voltage or current range of the governor bias input signal must
be determined. If the programmed range does not match what is used by the governor bias
input, unpredictable or undesired system behavior could occur.
Settings for Governor Bias Output voltage or current range and polarity are found in
BESTCOMSPlus
® under SETTINGS EXPLORER > DGC-2020 > MULTIGEN
MANAGEMENT > GOVERNOR OUTPUT. See Figure 7-58.
Front Panel Navigation Path: SETTINGS > MULTIGEN MANAGEMENT > GOV ANALOG OUTPUT
i. Output Type - Select Voltage or Current, depending on the output type.
ii. Response - Select Increasing if a higher level of bias causes the governor to increase
generator output voltage; select Decreasing if a higher level of bias causes the
governor to decrease generator output voltage.
iii. Min Output Current (mA) - This setting defines the minimum governor bias current
level if the bias Output Type is set to Current.
iv. Max Output Current (mA) - This setting defines the maximum governor bias current
level if the bias Output Type is set to Current.
v. Min Output Voltage (V) - This setting defines the minimum governor bias voltage
level if the bias Output Type is set to Voltage.
vi. Max Output Voltage (V) - This setting defines the maximum governor bias voltage
level if the bias Output Type is set to Voltage.
Figure 7-58. Settings Explorer, Multigen Management, Governor Output Screen
e. Configure the kW and speed control parameters.
The settings for the kW and speed control parameters are found in BESTCOMSPlus
® under
SETTINGS EXPLORER > DGC-2020 > BIAS CONTROL SETTINGS > GOVERNOR BIAS
CONTROL SETTINGS. See Figure 7-59.
Front Panel Navigation Path: SETTINGS > BIAS CONTROL > GOV BIAS CONTROL
9400200990 Rev X
DGC-2020 Setup
7-51