Register

Description

Type

Units

Scaling

Factor

R/W

Range

46032

J1939-ADEC CAN bus
Speed Demand

Uint32

0.125 rpm/bit, 0 rpm
offset

N/A

R

0 - 8031.875

46034

J1939-ADEC Analog
Speed Demand

Uint32

0.125 rpm/bit, 0 rpm
offset

N/A

R

0 - 8031.875

46036

J1939-ADEC Speed
Demand Source

Uint32

0 = ANALOG_CAN,
1 = UP_DN_ECU, 2
= UP_DN_CAN, 3 =
ANALOG_ECU, 5 =
FREQUENCY, 7 =
NO_CAN_DEMAND

N/A

R

0 - 7

46038

J1939-ADEC Specified
Torque

Uint32

1 Nm/Bit, 0 Offset

N/A

R

0 to 64255 Nm

46040

J1939-ADEC Engine
Optimized

Uint32

No Scale or Offset

N/A

R

0 - 64255

46042

J1939-ADEC Current P
Degree

Uint32

0.0025%/Bit, 0
offset

N/A

R

0 to 160.7375%

46044

J1939-ADEC Day Tank
Fill Percent

Uint32

0.4%/Bit, 0 offset

N/A

R

0 to 100%

46046

J1939-ADEC Storage
Tank Fill Percent

Uint32

0.4%/Bit, 0 offset

N/A

R

0 - 4294967295

46048

J1939-ADEC Injection
Quantity

Uint32

0.1 mm2 per bit

N/A

R

0 - 429496729.5

46050

J1939-ADEC Engine
Power Reserve

Uint32

0.001% per bit

N/A

R

0 - 4294967.295

46052

J1939-ADEC Cylinder
Cutout Code

Uint32

No Scale or Offset

N/A

R

0 - 4294967295

46054

J1939-ADEC Start
Sequence Bit Field

Uint32

Bit Packed Data

N/A

R

0 - 4294967295

46056

J1939-ADEC P Lube Oil
Limit LO

Uint32

binary on or off

N/A

R

0 - 1

46058

J1939-ADEC P Lube Oil
Limit LO LO

Uint32

binary on or off

N/A

R

0 - 1

46060

J1939-ADEC P Charge
Air Pressure

Uint32

.01 mbar/bit, 0
offset

N/A

R

0 - 42949672.5 mbar

45062

J1939-ADEC AL Power
Amp 1 Fail Bit Fld

Uint32

Bit Packed Data

N/A

R

0 - 4294967295

46064

J1939-ADEC AL Power
Amp 2 Fail Bit Fld

Uint32

Bit Packed Data

N/A

R

0 - 4294967295

46066

J1939-ADEC AL
Transistor Out Bit Fl

Uint32

Bit Packed Data

N/A

R

0 - 4294967295

46068

J1939-ADEC Camshaft
RPM

Uint32

0.1 rpm/bit, 0 offset

N/A

R

0 - 429496729.5 rpm

46070

J1939-ADEC Daily Fuel
Consumption

Uint32

.0001 m3 per bit, 0
offset

N/A

R

0 - 429496.7295 m3

46072

J1939-ADEC Frequency
Speed Demand.

Uint32

0.1 rpm/bit, 0 offset

N/A

R

0 - 429496729.5 rpm

46074

J1939-ADEC Average
Trip Fuel Consumption

Uint32

0.001 L/h/bit, 0
offset

N/A

R

0 - 4294967.295 L/h

46076

J1939-ADEC Injection
Quantity DBR Pct

Uint32

0,01% /bit, 0 offset

N/A

R

0 - 42949672.95 %

46078

J1939-ADEC Actual
Droop

Uint32

0.001%/bit, 0 offset

N/A

R

0 - 4294967.295 %

46080

J1939-ADEC Nodes On
CAN bus

Uint32

No Scale or Offset

N/A

R

0 - 4294967295

46082

J1939-ADEC Lost
Nodes on CAN bus

Uint32

No Scale or Offset

N/A

R

0 - 4294967295

46084

J1939-ADEC Trip
Operating Time

Uint32

No Scale or Offset

N/A

R

0 - 4294967295 h