beautypg.com

Basler Electric DGC-2020 User Manual

Page 297

background image

Figure 7-12. Settings Explorer, Alarm Configuration, Pre-Alarms Screen

Alarms
Front Panel Navigation Path: SETTINGS > ALARM CONFIGURATION > ALARMS

Examine each of the alarms. Alarm setup is not required to operate the machine, but is likely to be
desired to provide shutdowns for machine protection. Enable any desired alarms and enter an appropriate
threshold. Set the Activation Delay where possible. The activation delay is the duration that a condition
remains in effect before annunciating an alarm. Refer to the appropriate paragraphs in Section 4,
BESTCOMSPlus

® Software, for additional information regarding alarm configuration. See Figure 7-13.

Figure 7-13. Settings Explorer, Alarm Configuration, Alarms Screen

Sender Fail
Front Panel Navigation Path: SETTINGS > ALARM CONFIGURATION > SENDER FAIL

Enable each sender type as desired by configuring it as an alarm or pre-alarm. Set an activation delay.
The activation delay is the duration that the condition remains in effect before annunciating an alarm or
pre-alarm. Refer to the appropriate paragraphs in Section 4, BESTCOMSPlus

® Software, for additional

information regarding sender fail configuration. If a DGC-2020 is receiving engine information from an

9400200990 Rev X

DGC-2020 Setup

7-9

This manual is related to the following products: