Synchronizer Active for a Short Time, Then Stops

Step 1: Check if a Sync Fail pre-alarm or a Breaker Close Fail pre-alarm is occurring or has occurred.

The synchronizer stops acting when such a pre-alarm occurs. Press the Off button or the Reset
button on the DGC-2020 front panel to clear these pre-alarms.

Step 2: Verify that the Sync Fail Activation delay is sufficiently long to allow the synchronizer to

complete the synchronization process.

Step 3: Verify that the Breaker Close Wait time is not too short causing a pre-alarm to occur before the

breaker closes when a breaker close is initiated by the DGC-2020.

Synchronizer Does Not Lower Engine Speed Allowing Alignment of Bus and Generator

Step 1: Using the front panel HMI, navigate to the SETTINGS > MULTIGEN MANAGEMENT > GOV

ANALOG OUTPUT screen and set SPD RESPONSE to DECREASING.

Synchronizer Does Not Raise Engine Speed Allowing Alignment of Bus and Generator

Step 1: Using the front panel HMI, navigate to the SETTINGS > MULTIGEN MANAGEMENT > GOV

ANALOG OUTPUT screen and set SPD RESPONSE to DECREASING.

Synchronizer Does Not Lower the Generator Voltage to Achieve Matching of Bus and Generator
Voltages

Step 1: Navigate to the SETTINGS > MULTIGEN MANAGEMENT > AVR ANALOG OUTPUT screen

and set VOLT RESPONSE to DECREASING.

Synchronizer Does Not Raise Generator Voltage to Achieve Matching of Bus and Generator
Voltages

Step 1: Navigate to the SETTINGS > MULTIGEN MANAGEMENT > AVR ANALOG OUTPUT screen

and set VOLT RESPONSE to DECREASING.

Speed Bias

Engine Speed Does Not Change When Speed Bias Voltage Changes

Step 1: Verify that the engine speed will change when the speed bias changes. As a test, you can force

a voltage on the speed bias output by setting the Min Output Voltage and Max Output Voltage
to the same value by navigating to SETTINGS > MULTIGEN MANAGEMENT > GOV ANALOG
OUPUT. If the bias is current based, you can force a fixed current by setting the Governor
Output Current Minimum and Maximum to the same value by navigating to SETTINGS >
MULTIGEN MANAGEMENT > GOV ANALOG OUTPUT.

If the speed still does not change when varying the bias:

Verify that the governor or ECU is equipped and configured to accept bias inputs.

Check connections to verify the wiring to the governor bias is correct.

If you have an engine with an ECU, check ECU programming to verify it is set up to
accept a speed bias input.

Engine Speed Decreases When Speed Bias is Increased

Step 1: Navigate to the SETTINGS > MULTIGEN MANAGEMENT > GOV ANALOG OUTPUT screen

and set SPD RESPONSE to DECREASING.

Engine Speed Increases When Speed Bias is Decreased

Step 1: Navigate to the SETTINGS > MULTIGEN MANAGEMENT > GOV ANALOG OUTPUT screen

and set SPD RESPONSE to DECREASING.

Voltage Bias

Generator Voltage Does Not Change When Voltage Bias Changes

Step 1: As a test, you can force a voltage on the AVR bias output by setting the Min Output Voltage

and Max Output Voltage to the same value by navigating to SETTINGS > MULTIGEN
MANAGEMENT > AVR OUTPUT. If the bias is current based, you can force a fixed current by
setting the Min Output Current and Max Output Current to the same value by navigating to
SETTINGS > MULTIGEN MANAGEMENT > AVR OUTPUT.

9400200990 Rev X

DGC-2020 Maintenance and Troubleshooting