This product conforms to the following Harmonized Standards:

EN 50178:1997 - Electronic Equipment for use in Power Installations

EN 61000-6-4:2001 - Electromagnetic Compatibility (EMC), Generic Standards, Emission
Standard for Industrial Environments

EN 61000-6-2:2001 - Electromagnetic Compatibility (EMC), Generic Standards, Immunity for
Industrial Environments

Physical

Weight

CEM-2020 ........................... 2.25 lb (1.02 kg)

CEM-2020H ........................ 1.90 lb (0.86 kg)

Dimensions ................................ See Installation later in this section.

Functional Description

Contact Inputs

The CEM-2020 provides 10 programmable contact inputs with the same functionality as the contact
inputs on the DGC-2020. The label text of each contact input is customizable.

Contact Outputs

CEM-2020

The CEM-2020 provides 24 programmable contact outputs with the same functionality as the contact
outputs on the DGC-2020. Outputs 13 through 24 can carry 1 A. Outputs 25 through 36 can carry 4 A.
The label text of each contact output is customizable.

CEM-2020H

The CEM-2020H provides 18 programmable contact outputs with the same functionality as the contact
outputs on the DGC-2020. Outputs 13 through 24 can carry 2 A. Outputs 25 through 30 can carry 10 A.
The label text of each contact output is customizable.

NOTES

When using the DGC-2020 synchronizer, it is recommended that local relay
outputs on the DGC-2020 be used for breaker close commands to minimize
the possibility of closures outside of desired breaker closing angles.

If remote (CEM-2020) outputs are to be used for breaker close commands, it is
recommended that the anticipatory synchronizer type be used, and the breaker
close wait time be adjusted to account for possible CEM-2020 output delays
(typically 50 ms) to achieve desired breaker closing angles.

Communications

CAN Bus

A Control Area Network (CAN) is a standard interface that enables communication between the CEM-
2020 and the DGC-2020.

BESTCOMSPlus

® Software

BESTCOMSPlus

® provides the user with a point-and-click means to set and monitor the Contact

Expansion Module. Installation and operation of BESTCOMSPlus

® is described in Section 4,

BESTCOMSPlus

® Software.

Installation

Contact Expansion Modules are delivered in sturdy cartons to prevent shipping damage. Upon receipt of
a module, check the part number against the requisition and packing list for agreement. Inspect for

9400200990 Rev X

DGC-2020 CEM-2020 (Contact Expansion Module)

10-3