Name

Description

Symbol

Generator
Protection

51-3

True when the 51-3 element is configured as a pre-
alarm and has tripped.

Generator
Protection

78

True when the 78 element is configured as a pre-
alarm and has tripped.

Generator
Protection

81 ROC DF/DT

True when the 81 ROC DF/DT element is configured
as a pre-alarm and has tripped.

Generator
Protection

81 Over

True when the 81 Over element is configured as a
pre-alarm and has tripped.

Generator
Protection

81 Under

True when the 81 Under element is configured as a
pre-alarm and has tripped.

Global Pre-Alarm

True when one or more pre-alarms are set.

Hi Coolant Temp

True when the High Coolant Temp Pre-Alarm
threshold has been exceeded.

High Exhaust
Temperature

True when Diesel Particulate Filter (DPF) lamp
status broadcast over CANBus indicates high
exhaust temperature.

High Fuel Level

True when the High Fuel Level Pre-Alarm settings
have been exceeded.

Intergenset
Comm Fail

True when an individual generator detects that it had
been connected to a generator network, but has lost
the connection.

Load Share
Module

Load Share
Module Comm
Fail

True when communication from the LSM-2020 to the
DGC-2020 has been lost.

Load Share
Module

Multiple Load
Share Modules
Detected

True when more than one LSM-2020 is connected.

Low Battery
Voltage

True when the Low Battery Voltage Pre-Alarm
settings have been exceeded.

Low Coolant
Level

True when the Low Coolant Level function is
configured as a pre-alarm and the activation delay
has expired. In addition, true when CANBus is
enabled and the Low Coolant Level Pre-Alarm
threshold has been exceeded.

Low Coolant
Temp

True when the Low Coolant Temp Pre-Alarm
threshold has been exceeded.

Low Fuel Level

True when the Low Fuel Level Pre-Alarm threshold
has been exceeded.

9400200990 Rev X

DGC-2020 BESTlogic

Plus Programmable Logic

5-15