Name
Description
Symbol
Generator
Protection
51-3
True when the 51-3 element is configured as a pre-
alarm and has tripped.
Generator
Protection
78
True when the 78 element is configured as a pre-
alarm and has tripped.
Generator
Protection
81 ROC DF/DT
True when the 81 ROC DF/DT element is configured
as a pre-alarm and has tripped.
Generator
Protection
81 Over
True when the 81 Over element is configured as a
pre-alarm and has tripped.
Generator
Protection
81 Under
True when the 81 Under element is configured as a
pre-alarm and has tripped.
Global Pre-Alarm
True when one or more pre-alarms are set.
Hi Coolant Temp
True when the High Coolant Temp Pre-Alarm
threshold has been exceeded.
High Exhaust
Temperature
True when Diesel Particulate Filter (DPF) lamp
status broadcast over CANBus indicates high
exhaust temperature.
High Fuel Level
True when the High Fuel Level Pre-Alarm settings
have been exceeded.
Intergenset
Comm Fail
True when an individual generator detects that it had
been connected to a generator network, but has lost
the connection.
Load Share
Module
Load Share
Module Comm
Fail
True when communication from the LSM-2020 to the
DGC-2020 has been lost.
Load Share
Module
Multiple Load
Share Modules
Detected
True when more than one LSM-2020 is connected.
Low Battery
Voltage
True when the Low Battery Voltage Pre-Alarm
settings have been exceeded.
Low Coolant
Level
True when the Low Coolant Level function is
configured as a pre-alarm and the activation delay
has expired. In addition, true when CANBus is
enabled and the Low Coolant Level Pre-Alarm
threshold has been exceeded.
Low Coolant
Temp
True when the Low Coolant Temp Pre-Alarm
threshold has been exceeded.
Low Fuel Level
True when the Low Fuel Level Pre-Alarm threshold
has been exceeded.