Figure 7-48. Settings Explorer, Multigen Management, AVR Output Screen
Settings should be entered for each of the following parameters when appropriate:
a. Output Type - Select whether the AVR bias signal should be Voltage or Current.
b. Response - Select Increasing or Decreasing. Increasing should be selected if an increase in
the output parameter results in an increase of generator output voltage.
c. Min Output Current (mA) and Max Output Current (mA) - If the Output Type is Current, these
parameters must be configured. Set the minimum and maximum current to a range equal to
the voltage bias input range for the voltage regulator. The range on these parameters is 4 ma
to 20 ma.
d. Min Output Voltage (V) and Max Output Voltage (V) - If the Output Type is Voltage, these
parameters must be configured. Set the minimum and maximum voltage to a range equal to
the voltage bias input range for the voltage regulator. The range on these parameters is
−10V
to +10V.
11. Next click on Governor Output and select the appropriate bias output parameters as required by the
speed governor. These parameters are identical to those of the AVR output, and should be set in a
similar manner. See Figure 7-49.
Front Panel Navigation Path: SETTINGS > MULTIGEN MANAGEMENT > GOV ANALOG OUTPUT
Figure 7-49. Settings Explorer, Multigen Management, Governor Output Screen
12. Set up programmable logic to allow the DGC-2020 to synchronize the generator and close the
generator breaker. In the BESTlogicPlus Programmable Logic, click on the Elements tab and drag the
Gen Breaker element into your main logic. See Figure 7-50.