System configuration and status, Rated volts, Pre-start contact config – Basler Electric DGC-2020 User Manual
Page 451: System units, Battery volts, Off mode status, Run mode status, Auto mode status, Virtual input 1 status, Virtual input 2 status
9400200990 Rev X
DGC-2020 Modbus
™ Communication
B-19
Register
Description
Type
Units
Scaling
Factor
R/W
Range
43480
User Configurable Input 7 Eng Run Only
Int32
N/A
N/A
RW
0 = Always
1 = While
Engine
Running Only
43482
User Configurable Input 8 Eng Run Only
Int32
N/A
N/A
RW
0 = Always
1 = While
Engine
Running Only
43484
User Configurable Input 9 Eng Run Only
Int32
N/A
N/A
RW
0 = Always
1 = While
Engine
Running Only
43486
User Configurable Input 10 Eng Run Only
Int32
N/A
N/A
RW
0 = Always
1 = While
Engine
Running Only
43488
User Configurable Input 11 Eng Run Only
Int32
N/A
N/A
RW
0 = Always
1 = While
Engine
Running Only
43490
User Configurable Input 12 Eng Run Only
Int32
N/A
N/A
RW
0 = Always
1 = While
Engine
Running Only
43492
User Configurable Input 13 Eng Run Only
Int32
N/A
N/A
RW
0 = Always
1 = While
Engine
Running Only
43494
User Configurable Input 14 Eng Run Only
Int32
N/A
N/A
RW
0 = Always
1 = While
Engine
Running Only
43496
User Configurable Input 15 Eng Run Only
Int32
N/A
N/A
RW
0 = Always
1 = While
Engine
Running Only
43498
User Configurable Input 16 Eng Run Only
Int32
N/A
N/A
RW
0 = Always
1 = While
Engine
Running Only
System Configuration and Status
Register
Description
Type
Units
Scaling
Factor
R/W
Range
43500
Rated Volts
Float
Volt
N/A
RW
1 - 99999
43502
Pre-Start Contact Config
Int32
N/A
N/A
RW
0 = Open After Disconnect
1 = Closed While Running
43504
System Units
Int32
N/A
N/A
RW
0 = English
1 = Metric
43506
Battery Volts
Int32
N/A
N/A
RW
0 = 12V
1 = 24V
43508
Off Mode Status
Int32
N/A
N/A
R
0 = Disable
1 = Enable
43510
Run Mode Status
Int32
N/A
N/A
R
0 = Disable
1 = Enable
43512
Auto Mode Status
Int32
N/A
N/A
R
0 = Disable
1 = Enable
43514
Virtual Input 1 Status
Int32
N/A
N/A
R
0 = Disable
1 = Enable
43516
Virtual Input 2 Status
Int32
N/A
N/A
R
0 = Disable
1 = Enable
43518
Virtual Input 3 Status
Int32
N/A
N/A
R
0 = Disable
1 = Enable
43520
Virtual Input 4 Status
Int32
N/A
N/A
R
0 = Disable
1 = Enable
43522
RTC Clock Hour
Int32
Hour
N/A
RW
0 - 23