Basler Electric DGC-2020 User Manual
Page 11
![background image](https://www.manualsdir.com/files/773941/content/doc011.png)
BESTCOMSPlus®
Version and Date
Change
1.03.00, 08/07
•
Added/Updated screens to support firmware package version 1.03.00.
(See firmware package version history for details.)
•
Added password protection for portions of the programmable logic.
•
Made all status LEDs available as inputs for PLC logic.
1.02.00, 05/07
•
Added Spanish language support.
•
Added Clock Setup screen.
•
Changed layout of several screens.
1.01.02, 04/07
•
Removed International Modem option from Style Chart.
1.01.01, 02/07
•
Added Chinese language support.
1.00.07, 11/06
•
Initial release
Firmware Package
Version and Date
Change
1.19.00, 10/14
•
Modified Voltage Trim function to support paralleling of reconfigurable
machines.
•
Added MTU Speed Demand Switch setting from logic capability.
•
Added a rest timer for cyclic cranking.
•
Added Mains Fail Return Fail pre-alarm and Mains Fail Max Return
Time setting.
•
Added a deadband setting for speed trim and voltage trim.
•
Added Parallel to Mains Gain Factor for mains parallel operation.
•
Added System kW Generation in percent to Gen Status screen and
configurable protection.
•
Added System Total Capacity on Generator Network Status screen.
•
Added DPF Outlet Gas Temperature to J1939 metering and
configurable protection.
•
Added John Deere to list of ECU configurations.
•
Added AEM thermal protection settings to Modbus.
•
Changed DEF EMPTY pre-alarm to DEF LOW SEVERE.
•
Changed DEF ENGINE DERATE pre-alarm to DEF INDUCEMENT.
•
Added descriptive text for Diagnostic Trouble Codes (DTC’s)
broadcast by Mercedes, PSI, and MTU-ECU9 engine ECU’s.
•
Added ECU9 Fault Code list for MTU.
1.18.02, 04/14
•
Added German and Portuguese language support.
•
Added DGC-2000 legacy Modbus option.
•
Added Breaker configuration one-line diagram and mains fail transfer
status screen to front panel.
•
Increased unique recorded events to 50 from 30.
1.17.07, 05/13
•
Minor firmware improvements
1.17.02, 03/13
•
Added new breaker hardware and mains fail transfer settings.
•
Improved breaker hardware, synch check, and mains fail logic.
•
Added a logic element which allows the EPS Supplying Load front
panel LED to be driven via logic.
•
Improved event log processing rate.
•
Improved CAN transmit processing rate.
•
Added single-phase AC bus sensing configuration option.
•
Corrected battle override function preventing engine shut-off in rare
cases.
•
Corrected DTCs not clearing when receiving a “no active” DTC frame.
•
Corrected frequency settings reverting to 60 Hz on startup for 400 Hz
units.