Basler Electric DGC-2020 User Manual
Page 240
Name
Description
Symbol
Analog
Expansion
Module
Remote RTD
Inputs 1-8
True when Over 1, Over 2, Under 1, Under 2, or Out
of Range is configured as a pre-alarm and the
threshold has been exceeded. (Over 1 shown.)
Analog
Expansion
Module
Remote
Thermocouple
Inputs 1-2
True when Over 1, Over 2, Under 1, or Under 2 is
configured as a pre-alarm and the threshold has
been exceeded. (Over 1 shown.)
Battery Charger
Fail
True when the Battery Charger Fail function is
configured as a pre-alarm and the activation delay
has expired.
Battery
Overvoltage
True when the Battery Overvoltage pre-alarm
threshold has been exceeded.
Checksum
Failure
True when some of the user settings or firmware
code has been corrupted. Refer to Section 4,
BESTCOMSPlus
® Software, Alarm Configuration,
Pre-Alarms, for more details.
Configurable
Protection
Protection 1-8
True when Over 1, Over 2, Under 1, or Under 2 is
configured as a pre-alarm and the threshold has
been exceeded. (Over 1 shown.)
Contact
Expansion
Module
Multiple Contact
Expansion
Modules
Connected
True when more than one CEM-2020 is connected.
Contact
Expansion
Module
Contact
Expansion
Module Comm
Fail
True when communication from the CEM-2020 to the
DGC-2020 has been lost.
Contact
Expansion
Module
Contact
Expansion
Modules
Hardware
Mismatch
True when the connected CEM-2020 does not have
the same number of outputs as defined on the
System Parameters, Remote Module Setup screen
in BESTCOMSPlus.
Coolant Temp
Sender Fail
True when the Coolant Temp Sender Fail is
configured as a pre-alarm and the activation delay
has expired.
DEF Fluid Low
True when the engine ECU reports via CANBus that
the Diesel Exhaust Fluid (DEF) is at a level between
8 and 23%.
5-12
DGC-2020 BESTlogic
™
Plus Programmable Logic
9400200990 Rev X