Name

Description

Symbol

Analog
Expansion
Module

Remote RTD
Inputs 1-8

True when Over 1, Over 2, Under 1, Under 2, or Out
of Range is configured as a pre-alarm and the
threshold has been exceeded. (Over 1 shown.)

Analog
Expansion
Module

Remote
Thermocouple
Inputs 1-2

True when Over 1, Over 2, Under 1, or Under 2 is
configured as a pre-alarm and the threshold has
been exceeded. (Over 1 shown.)

Battery Charger
Fail

True when the Battery Charger Fail function is
configured as a pre-alarm and the activation delay
has expired.

Battery
Overvoltage

True when the Battery Overvoltage pre-alarm
threshold has been exceeded.

Checksum
Failure

True when some of the user settings or firmware
code has been corrupted. Refer to Section 4,
BESTCOMSPlus

® Software, Alarm Configuration,

Pre-Alarms, for more details.

Configurable
Protection

Protection 1-8

True when Over 1, Over 2, Under 1, or Under 2 is
configured as a pre-alarm and the threshold has
been exceeded. (Over 1 shown.)

Contact
Expansion
Module

Multiple Contact
Expansion
Modules
Connected

True when more than one CEM-2020 is connected.

Contact
Expansion
Module

Contact
Expansion
Module Comm
Fail

True when communication from the CEM-2020 to the
DGC-2020 has been lost.

Contact
Expansion
Module

Contact
Expansion
Modules
Hardware
Mismatch

True when the connected CEM-2020 does not have
the same number of outputs as defined on the
System Parameters, Remote Module Setup screen
in BESTCOMSPlus.

Coolant Temp
Sender Fail

True when the Coolant Temp Sender Fail is
configured as a pre-alarm and the activation delay
has expired.

DEF Fluid Low

True when the engine ECU reports via CANBus that
the Diesel Exhaust Fluid (DEF) is at a level between
8 and 23%.

5-12

DGC-2020 BESTlogic

Plus Programmable Logic

9400200990 Rev X