Basler Electric DGC-2020 User Manual
Page 541

9400200990 Rev X
DGC-2020 Modbus
™ Communication
B-109
Register
Description
Type
Units
Scaling
Factor
R/W
Range
46706
AEM Output 4 Max
Voltage
Int32
DeciVolt
Deci
RW
0 – 100
46708
AEM Output 4 Max
Current
Int32
Milliamp x 10
Deci
RW
40 – 200
46710
AEM Output 4 Min
Voltage
Int32
DeciVolt
Deci
RW
0 – 100
46712
AEM Output 4 Min
Current
Int32
Milliamp x 10
Deci
RW
40 – 200
46714
AEM Output 4 Param
Max
Int32
Centi Unit
Centi
RW
(-100000000) – 99999900
46716
AEM Output 4 Param
Min
Int32
Centi Unit
Centi
RW
(-100000000) – 99999900
This manual is related to the following products: