Modem setup (optional), Modem setup (optional) -28, Figure 4-22. voltage regulator setup -28 – Basler Electric DGC-2020 User Manual
Page 138
Figure 4-22. Voltage Regulator Setup
A
CAN bus Type: Select None, Marathon, Basler, or J1939
B
Primary Voltage Setpoint: Adjustable from 100 to 600 in increments of 0.1
C
Alternate Voltage Setpoint: Adjustable from 100 to 600 in increments of 0.1
D
Voltage Adjust Bandwidth: Adjustable from 0 to 3000 in increments of 1
E
Field Current Setting: Adjustable from 0 to 3000 in increments of 1
F
Primary Underfrequency Knee: Adjustable from 40 to 70 in increments of 0.1
G
Alternate Underfrequency Knee: Adjustable from 40 to 70 in increments of 0.1
H
Underfrequency Slope: Adjustable from 100 to 500 in increments of 1
Modem Setup (Optional)
DGC-2020 hardware version 3 controllers with style number xxxxxExxx are equipped with an RS-232
port. This port allows communication with an external, user-supplied modem with dial-in and dial-out
capability. DGC-2020 hardware versions 1 and 2 with style number xxxxxMxxx are equipped with an
internal modem with dial-in and dial-out capability.
A modem gives the DGC-2020 the ability to dial up to four telephone numbers
A
and annunciate user-
selected conditions to specified pagers
B
. These user-selected conditions include
C
:
•
27-1 Trip Alarm
•
27-2 Trip Alarm
•
32 Trip Alarm
•
40 Trip Alarm
•
47 Trip Alarm
•
51-1 Trip Alarm
•
51-2 Trip Alarm
•
51-3 Trip Alarm
•
59-1 Trip Alarm
•
59-2 Trip Alarm
•
81O Trip Alarm
•
81U Trip Alarm
•
27-1 Trip Pre-Alarm
•
27-2 Trip Pre-Alarm
•
32 Trip Pre-Alarm
•
40 Trip Pre-Alarm
•
47 Trip Pre-Alarm
•
51-1 Trip Pre-Alarm
•
51-2 Trip Pre-Alarm
•
51-3 Trip Pre-Alarm
•
59-1 Trip Pre-Alarm
•
59-2 Trip Pre-Alarm
•
78 Vector Shift Trip
•
81O Trip Pre-Alarm
•
81U Trip Pre-Alarm
•
81 ROCOF Trip
•
AEM Comm Failure
•
Auto Restart Failure Alarm
•
DPF Regeneration Required
•
DPF Soot Level High Pre-Alarm
•
DPF Soot Lvl Moderately High Pre-Alarm
•
DPF Soot Level Severely High Pre-Alarm
•
Duplicate AEM Pre-Alarm
•
Duplicate CEM Pre-Alarm
•
Duplicate LSM Pre-Alarm
•
ECU Shutdown Alarm
•
Emergency Stop Alarm
•
Engine Running
•
Fuel Leak Detect Status
•
Fuel Level Sender Fail Alarm
•
Fuel Level Sender Fail Pre-Alarm
•
GOV Output Limit
•
High Coolant Temperature Alarm
•
High Coolant Temp Pre-Alarm
•
High Exhaust Temperature
•
High Fuel Pre-Alarm
•
ID Missing Pre-Alarm
•
ID Repeat Pre-Alarm
•
Intergenset Comms Failure
•
kW Overload 1 Pre-Alarm
•
kW Overload 2 Pre-Alarm
•
kW Overload 3 Pre-Alarm
•
Loss of ECU Coms Alarm
•
Loss of ECU Coms Pre-Alarm
•
Loss of Generator Voltage Sensing Alarm
•
Low Battery Voltage Pre-Alarm
4-28
DGC-2020 BESTCOMSPlus
® Software
9400200990 Rev X