INTRODUCTION
The BE350 analog voltage controller regulates voltage on a
50 or 60 hertz brushless generator. Controller features
include frequency compensation, solid-state buildup
circuitry, and EMI filtering.
SPECIFICATIONS
Output Power
Maximum Continuous:
3.5 Adc at 73 Vdc (255 W)
One-Minute Forcing:
5 Adc at 105 Vdc (525 W) with
240 Vac power input
Exciter Field DC Resistance
Minimum:
21 Ω
Input Power
Range:
190–240 Vac, ±10%, 1-phase
Frequency:
50/60 Hz, ±10%
Burden:
500 VA
Sensing Input
Common with ac power input: 190–240 Vac, single-phase,
50/60 Hz, ±10%
Fuse
Bussmann GDC-4A or equivalent
Rating:
4 Aac, 250 Vac
Type:
Glass tube, 5 x 20 mm, time
delayed
Voltage Adjustment Range
171 to 264 Vac
Regulation Accuracy
Better than ±1.0%, no-load to full-load
Response Time
Less than 1.5 cycles for ±5% change in sensing voltage
EMI Suppression
Internal electromagnetic interference (EMI) filtering
Voltage Buildup
Automatic voltage buildup occurs for residual generator
voltages as low as 10 Vac.
Power Dissipation
8 W maximum
Temperature
Operating:
–40 to 60°C (–40 to 140°F)
Storage:
–65 to 85°C (–85 to 185°F)
Vibration
2 to 27 Hz:
1.3 G
27 to 52 Hz:
0.914 mm, double-amplitude
52 to 1000 Hz:
5 G
Shock
Withstands up to 20 G in each of three mutually
perpendicular axes.
Weight
184 g (6.5 oz) net
Agency Certification
UL recognized and CSA certified
CONTROLS
BE350 controls consist of jumpers and screwdriver-
adjusted potentiometers.
Potentiometer Controls
BE350 potentiometer controls are accessible through the
controller front panel and are shown in Figure 1.
This control raises and lowers the generator output voltage.
VOLT Control
This control adjusts the stability by increasing and reducing
the response time of the BE350.
STAB Control
This control adjusts the corner frequency point of the
BE350 frequency compensation characteristic.
U/F Control
Jumpers
Two jumpers control BE350 operation: the Corner
Frequency jumper and the Voltage Adjust Rheostat jumper.
These jumpers are shown in Figure 2.
BE350 controllers are delivered with the Corner Frequency
jumper set for 60 hertz operation. This gives a corner
frequency of 55 hertz. For 50 hertz operation and a corner
frequency of 45 hertz, the Corner Frequency jumper must
be move to the 50 Hz terminal.
Corner Frequency Jumper
BE350 controllers are delivered with the Voltage Adjust
Rheostat jumper connected across terminals 6 and 7. This
enables adjustment of the generator output voltage through
the controller’s internal Voltage Control potentiometer.
Clockwise rotation of the Voltage Control potentiometer
increases the generator voltage.
Voltage Adjust Rheostat Jumper
If remote adjustment of the generator output is desired, the
Voltage Adjust Rheostat jumper must be replaced with a
user-supplied rheostat. A 2000 ohm, ½ watt rheostat will
provide adequate voltage adjustment for most applications.
Figure 6 shows the proper remote rheostat connections.
INPUT POWER/SENSING INPUT
Power for the exciter field and BE350 is derived from the
generator output. The acceptable power input range is 171
to 264 Vac. Connect the input power wiring to terminals 3
and 4 as shown in Figure 5.
EXCITER FIELD POWER CIRCUIT
Controller terminal F+ is connected to the brushless exciter
field positive terminal and controller terminal F– is
connected to the brushless exciter field negative terminal.