Register
Description
Type
Units
Scaling
Factor
R/W
Range
45106
Active DTC 1
Uint32
N/A
N/A
R
Suppose the 32 bits of DTC Data is
in Register N and N+1.
SPN = (Register N: Most
Significant 3 bits * 65536) +
(Register N+1: LS Byte * 256) +
(Register N+1: MS Byte)
FMI = Register N: Bits 8-12
Occurrence Count = Register N:
Bits 0 through 6
45108
Active DTC 2
Uint32
N/A
N/A
R
45110
Active DTC 3
Uint32
N/A
N/A
R
45112
Active DTC 4
Uint32
N/A
N/A
R
45114
Active DTC 5
Uint32
N/A
N/A
R
45116
Active DTC 6
Uint32
N/A
N/A
R
45118
Active DTC 7
Uint32
N/A
N/A
R
45120
Active DTC 8
Uint32
N/A
N/A
R
45122
Active DTC 9
Uint32
N/A
N/A
R
45124
Active DTC 10
Uint32
N/A
N/A
R
45126
Active DTC 11
Uint32
N/A
N/A
R
45128
Active DTC 12
Uint32
N/A
N/A
R
45130
Active DTC 13
Uint32
N/A
N/A
R
45132
Active DTC 14
Uint32
N/A
N/A
R
45134
Active DTC 15
Uint32
N/A
N/A
R
45136
Active DTC 16
Uint32
N/A
N/A
R
45138
Previously Active DTC 1
Uint32
N/A
N/A
R
45140
Previously Active DTC 2
Uint32
N/A
N/A
R
45142
Previously Active DTC 3
Uint32
N/A
N/A
R
41544
Previously Active DTC 4
Uint32
N/A
N/A
R
45146
Previously Active DTC 5
Uint32
N/A
N/A
R
45148
Previously Active DTC 6
Uint32
N/A
N/A
R
45150
Previously Active DTC 7
Uint32
N/A
N/A
R
45152
Previously Active DTC 8
Uint32
N/A
N/A
R
45154
Previously Active DTC 9
Uint32
N/A
N/A
R
45156
Previously Active DTC
10
Uint32
N/A
N/A
R
45158
Previously Active DTC
11
Uint32
N/A
N/A
R
45160
Previously Active DTC
12
Uint32
N/A
N/A
R
45162
Previously Active DTC
13
Uint32
N/A
N/A
R
45164
Previously Active DTC
14
Uint32
N/A
N/A
R
45166
Previously Active DTC
15
Uint32
N/A
N/A
R
45168
Previously Active DTC
16
Uint32
N/A
N/A
R
45170
Active DTC Count Data
Uint32
N/A
N/A
R
0 - 16
45172
Previously Active DTC
Count Data
Uint32
N/A
N/A
R
0 - 16
45174
Active MTU Fault Code
Count Data
Uint32
N/A
N/A
R
0 - 20
45176-
248
RESERVED
45250
CAN bus Enabled by
User Data
Int32
N/A
N/A
RW
0 - 1
45252
DTC Enable Data
Int32
N/A
N/A
RW
0 - 1
45254
J1939 Source Address
Int32
N/A
N/A
RW
1 - 253
45256
ECU Control Output
Uint32
N/A
N/A
RW
0 = Fuel Relay Controls
1 - Preheat Relay Controls
45258
Pulsing Enable
Uint32
N/A
N/A
RW
1 = Enable
2 = Disable
45260
MDEC Module Type
Uint32
N/A
N/A
RW
1 = CAN Module 201
2 = CAN Module 302
3 = CAN Module 303
4 = CAN Module 304