beautypg.com

Active dtc 1, Active dtc 2, Active dtc 3 – Basler Electric DGC-2020 User Manual

Page 488: Active dtc 4, Active dtc 5, Active dtc 6, Active dtc 7, Active dtc 8, Active dtc 9, Active dtc 10

background image

B-56

DGC-2020 Modbus

™ Communication

9400200990 Rev X

Register

Description

Type

Units

Scaling

Factor

R/W

Range

45106

Active DTC 1

Uint32

N/A

N/A

R

Suppose the 32 bits of DTC Data is
in Register N and N+1.

SPN = (Register N: Most
Significant 3 bits * 65536) +
(Register N+1: LS Byte * 256) +
(Register N+1: MS Byte)

FMI = Register N: Bits 8-12

Occurrence Count = Register N:
Bits 0 through 6

45108

Active DTC 2

Uint32

N/A

N/A

R

45110

Active DTC 3

Uint32

N/A

N/A

R

45112

Active DTC 4

Uint32

N/A

N/A

R

45114

Active DTC 5

Uint32

N/A

N/A

R

45116

Active DTC 6

Uint32

N/A

N/A

R

45118

Active DTC 7

Uint32

N/A

N/A

R

45120

Active DTC 8

Uint32

N/A

N/A

R

45122

Active DTC 9

Uint32

N/A

N/A

R

45124

Active DTC 10

Uint32

N/A

N/A

R

45126

Active DTC 11

Uint32

N/A

N/A

R

45128

Active DTC 12

Uint32

N/A

N/A

R

45130

Active DTC 13

Uint32

N/A

N/A

R

45132

Active DTC 14

Uint32

N/A

N/A

R

45134

Active DTC 15

Uint32

N/A

N/A

R

45136

Active DTC 16

Uint32

N/A

N/A

R

45138

Previously Active DTC 1

Uint32

N/A

N/A

R

45140

Previously Active DTC 2

Uint32

N/A

N/A

R

45142

Previously Active DTC 3

Uint32

N/A

N/A

R

41544

Previously Active DTC 4

Uint32

N/A

N/A

R

45146

Previously Active DTC 5

Uint32

N/A

N/A

R

45148

Previously Active DTC 6

Uint32

N/A

N/A

R

45150

Previously Active DTC 7

Uint32

N/A

N/A

R

45152

Previously Active DTC 8

Uint32

N/A

N/A

R

45154

Previously Active DTC 9

Uint32

N/A

N/A

R

45156

Previously Active DTC
10

Uint32

N/A

N/A

R

45158

Previously Active DTC
11

Uint32

N/A

N/A

R

45160

Previously Active DTC
12

Uint32

N/A

N/A

R

45162

Previously Active DTC
13

Uint32

N/A

N/A

R

45164

Previously Active DTC
14

Uint32

N/A

N/A

R

45166

Previously Active DTC
15

Uint32

N/A

N/A

R

45168

Previously Active DTC
16

Uint32

N/A

N/A

R

45170

Active DTC Count Data

Uint32

N/A

N/A

R

0 - 16

45172

Previously Active DTC
Count Data

Uint32

N/A

N/A

R

0 - 16

45174

Active MTU Fault Code
Count Data

Uint32

N/A

N/A

R

0 - 20

45176-
248

RESERVED

45250

CAN bus Enabled by
User Data

Int32

N/A

N/A

RW

0 - 1

45252

DTC Enable Data

Int32

N/A

N/A

RW

0 - 1

45254

J1939 Source Address

Int32

N/A

N/A

RW

1 - 253

45256

ECU Control Output

Uint32

N/A

N/A

RW

0 = Fuel Relay Controls
1 - Preheat Relay Controls

45258

Pulsing Enable

Uint32

N/A

N/A

RW

1 = Enable
2 = Disable

45260

MDEC Module Type

Uint32

N/A

N/A

RW

1 = CAN Module 201
2 = CAN Module 302
3 = CAN Module 303
4 = CAN Module 304

This manual is related to the following products: