Figure 4-93 – Basler Electric DGC-2020 User Manual

Page 213

background image

Figure 4-93. Metering, Inputs, Remote Thermocouple Inputs

Remote Analog Input Values

When an optional AEM-2020 (Analog Expansion Module) is connected, the values of the scaled analog
inputs, raw analog inputs, RTD input temperatures, raw RTD inputs, thermocouple input temperatures,
and raw thermocouple inputs are shown on this screen.

For each analog input, the raw metered input value is displayed along with the scaled metered input
value. This is useful for checking if the AEM-2020 is seeing a valid raw input value (i.e. the raw 0 to 10 V
voltage input or 4 to 20 mA current input). The scaled value is the raw input scaled up to the range
specified by the Parameter Minimum and Parameter Maximum value parameters in the Remote Analog
Input settings. Refer to Figure 4-93.

Figure 4-94. Metering, Inputs, Remote Analog Input Values

The Calibrate button shown on the Remote Analog Input Values screen opens the Analog Input
Temperature Calibration screen shown in Figure 4-95. This screen is used to calibrate RTD inputs 1
through 8 and thermocouple inputs 1 and 2.

9400200990 Rev X

DGC-2020 BESTCOMSPlus

® Software

4-103