beautypg.com

Basler Electric DGC-2020 User Manual

Page 352

background image

CAUTION

The bus condition parameters are critical because they determine when a breaker can
be closed. The generator breaker can be closed when any one of the following is true:

The generator is stable and both breakers are open

The generator is stable and the bus is stable

The generator is stable, the bus is dead, and the dead bus close enable
setting is set to enabled

The generator is dead, the dead gen close enable setting is set to enabled, the
bus is dead, and the dead bus close enable setting is set to enabled

The mains breaker can be closed only when the generator is stable and both breakers
are open, or the generator is stable and the bus is stable.

Figure 7-67. Settings Explorer, Breaker Management, Bus Condition Detection Screen

7-64

DGC-2020 Setup

9400200990 Rev X

This manual is related to the following products: