9400200990 Rev X
DGC-2020 Modbus
™ Communication
B-53
Register
Description
Type
Units
Scaling
Factor
R/W
Range
44986
Generator Frequency
Int32
Hertz
Deci
R
0 - 4400
44988
Bus Frequency
Int32
Hertz
Deci
R
0 - 4400
44990
Power Factor
Int32
N/A
Centi
R
(-100) - 100
44992
Slip Frequency
Int32
N/A
Milli
R
(-450000) -450000
44994
Bus VAB
Int32
Volt
N/A
R
(-2147483648) – 2147483647
44996
Bus VBC
Int32
Volt
N/A
R
(-2147483648) – 2147483647
44998
Bus VCA
Int32
Volt
N/A
R
(-2147483648) – 2147483647
45000-01
ECU Lamp Status
Int32
N/A
N/A
R
Bit 0 = Protect
Bit 1 = Not Used
Bit 2 = Not Used
Bit 3 = Warning
Bit 4 = Stop
Bit 5 = Not Used
Bit 6 = Not Used
Bit 7 = Malfunction
Bit 8 = Not Used
Bit 9 = Not Used
Bit 10 = Not Used
Bit 11 = Not Used
Bit 12 = Not Used
Bit 13 = Not Used
Bit 14 = Not Used
Bit 15 = Not Used
Bit 16 = Not Used
Bit 17 = Not Used
Bit 18 = Not Used
Bit 19 = Not Used
Bit 20 = Not Used
Bit 21 = Not Used
Bit 22 = Not Used
Bit 23 = Not Used
Bit 24 = Not Used
Bit 25 = Not Used
Bit 26 = Not Used
Bit 27 = Not Used
Bit 28 = Not Used
Bit 29 = Not Used
Bit 30 = Not Used
Bit 31 = Not Used
45002
Number of DTC’s
Int32
N/A
N/A
R
(-32768) - 32767
45004-07
Reserved