background image

Parity ................................................. None
Stop Bits ........................................... 1
Terminals .......................................... 14 (A), 13 (B), and 12 (shield)

RDP-110

Minimum Wire Size ........................... 20 AWG
Maximum Wire Length ...................... 4,000 feet (1,219 meters)
Terminals .......................................... 6 (RDP TXD

–), 7 (RDP TXD+)

CAN

NOTES

1. If the DGC-2020 is providing one end of the J1939 bus, a 120

Ω, ½ watt

terminating resistor should be installed across terminals 48 (CANL) and 49
(CANH).

2. If the DGC-2020 is not part of the J1939 bus, the stub connecting the

DGC-2020 to the bus should not exceed 914 mm (3 ft) in length.

3. The maximum bus length, not including stubs, is 40 m (131 ft).

4. The J1939 drain (shield) should be grounded at one point only. If

grounded elsewhere, do not connect the drain to the DGC-2020.


Differential Bus Voltage .................... 1.5 to 3 Vdc
Maximum Voltage ............................. –32 to +32 Vdc with respect to negative battery terminal
Communication Rate ........................ 250 kb/s
Terminals .......................................... 48 (low), 49 (high), and 50 (shield)

Real-Time Clock

Clock has leap year and selectable daylight saving time correction. Backup capacitor and backup battery
sustain timekeeping during losses of DGC-2020 operating power.

Resolution ......................................... 1 s
Accuracy ...........................................

±1.73 s/d at 25°C

Clock Holdup

Battery Holdup Time ......................... Approximately 10 yrs
Battery Type ..................................... Rayovac BR2032, lithium, coin-type, 3 Vdc, 195 mAh

Basler Electric P/N 38526

CAUTION

Replacement of the backup battery for the real-time clock should be performed
only by qualified personnel.

Do not short-circuit the battery, reverse battery polarity, or attempt to recharge
the battery. Observe polarity markings on the battery socket while inserting a
new battery. The battery polarity must be correct in order to provide backup for
the real-time clock.

It is recommended that the battery be removed if the DGC-2020 is to be
operated in a salt-fog environment. Salt-fog is known to be conductive and
may short-circuit the battery.

NOTE

Failure to replace the battery with Basler Electric P/N 38526 may void the
warranty.

9400200990 Rev X

DGC-2020 General Information

1-11