Dst start month, Dst start day, Dst start week of month – Basler Electric DGC-2020 User Manual
Page 453: Dst start day of week, Dst start hour, Dst start minute, Dst end month, Dst end day, Dst end week of month, Dst end day of week

9400200990 Rev X
DGC-2020 Modbus
™ Communication
B-21
Register
Description
Type
Units
Scaling
Factor
R/W
Range
43600
DST Start Month
Int32
N/A
N/A
RW
1 = January
2 = February
3 = March
4 = April
5 = May
6 = June
7 = July
8 = August
9 = September
10 = October
11 = November
12 = December
43602
DST Start Day
Int32
N/A
N/A
RW
1 - 31
43604
DST Start Week of Month
In32
N/A
N/A
RW
0 = First
1 = Second
2 = Third
3 = Fourth
4 = Last
43606
DST Start Day of Week
Int32
N/A
N/A
RW
0 = Sunday
1 = Monday
2 = Tuesday
3 = Wednesday
4 = Thursday
5 = Friday
6 = Saturday
43608
DST Start Hour
Int32
N/A
N/A
RW
0 - 23
43610
DST Start Minute
Int32
N/A
N/A
RW
0 - 59
43612
DST End Month
Int32
N/A
N/A
RW
1 = January
2 = February
3 = March
4 = April
5 = May
6 = June
7 = July
8 = August
9 = September
10 = October
11 = November
12 = December
43614
DST End Day
Int32
N/A
N/A
RW
1 - 31
43616
DST End Week of Month
Int32
N/A
N/A
RW
0 = First
1 = Second
2 = Third
3 = Fourth
4 = Last
43618
DST End Day of Week
Int32
N/A
N/A
RW
0 = Sunday
1 = Monday
2 = Tuesday
3 = Wednesday
4 = Thursday
5 = Friday
6 = Saturday
43620
DST End Hour
Int32
N/A
N/A
RW
0 - 23
43622
DST End Minute
Int32
N/A
N/A
RW
0 - 59
43624
EPS Low Line Scale Factor
Float
N/A
N/A
RW
0.001 - 3
43626
Rated Power Factor
Float
Power Factor
N/A
RW
(-1) - 1
43628
Prestart Rest Configuration
Int32
N/A
N/A
RW
0 = Off During Rest
1 = On During Rest
2 = Preheat before Crank
43630
Oil Pressure Crank Disconnect
UInt32
N/A
N/A
RW
0 = Disable
1 = Enable
43632
Crank Disconnect Pressure
Uint32
PSI
Deci
RW
29 - 1500
43634
Crank Disconnect Pressure in
kPa
Uin32
kPa
Deci
RW
200 - 10345
43636
Power Up Delay
Uint32
Second
N/A
RW
0 - 60
43638
Auto Config Detect Enable
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
43640
Low Line Detect Threshold
Int32
Volt
N/A
RW
0 - 480