Programmable senders -10 – Basler Electric DGC-2020 User Manual

Page 298

background image

engine ECU, the sender fail for coolant temperature and oil pressure do not need configured because
they have no effect. They are appropriate for resistive senders only. See Figure 7-14.

Figure 7-14. Settings Explorer, Alarm Configuration, Sender Fail Screen

Programmable Senders

If a DGC-2020 receives engine information from an engine ECU, the programmable sender parameters
for the coolant temperature and oil pressure senders do not need to be configured because they have no
effect. They are appropriate for resistive senders only.

Coolant Temperature (Figure 7-15)

1. The coolant temperature sender can be configured by selecting one of the sender types that come as

a part of the BESTCOMSPlus

® sender library by clicking on Load Cool Settings File and selecting the

appropriate sender.

2. If no sender file matches the sender being used, the individual points that map resistance points to

coolant temperature may be modified by setting numeric values in the table, or by dragging the points
of the graph to the desired characteristic. Information on sender characteristics should be obtained
from the sender manufacturer.

3. Select Positive or Negative sender slope as required for the desired sender graph.

4. Click Save Cool Data to save the data in the current settings file.

5. If you want to save newly entered sender data as a sender library file, click Create Cool Settings File

and enter a file name and location to save the file.

6. Click the Send Settings button in BESTCOMSPlus

® to send the sender settings to the DGC-2020.

7-10

DGC-2020 Setup

9400200990 Rev X