1.18 aac for 1a cts, 7.75 aac for 5a cts – Basler Electric DGC-2020 User Manual
Page 565
9400200990 Rev X
DGC-2020 Modbus
™ Communication
B-133
Holding
Register
Parameter
Range
Read/Write
Supported
Data
Format
Units
40471
Speed Upper Limit
0 to 2500 rpm
R
Raw ECU Parameter Data
10 rpm/bit gain, 0 rpm offset
40472
Torque Lower Limit
0 to 125%
R
Raw ECU Parameter Data
1%/bit gain, -125% offset
40473
Torque Upper Limit
0 to 125%
R
Raw ECU Parameter Data
1%/bit gain, -125% offset
40474
Crankcase Pressure
-250 to +251.99
kPa
R
Raw ECU Parameter Data
0.0078125 kPa/bit gain,
-250 kPa offset
40475
Oil Filter Diff. Pressure
0 to 125 kPa
R
Raw ECU Parameter Data
0.5 kPa/bit gain, 0 offset
40476
Fuel Filter Diff. Pressure
0 to 500 kPa
R
Raw ECU Parameter Data
2 kPa/bit gain, 0 offset
40477-82
FUTURE USE
40493-99
FUTURE USE
40500
DGC-2020 product series identifier
2020
R
40501
Firmware Part Number - 2nd most
significant digit. NOTE: The most
significant digit is always 9, but is
not mapped.
0 - 9
R
40502
Firmware Part Number - 3rd-6th
most significant digits
0000 - 9999
R
40503
Firmware Part Number - four least
significant digits
0000 - 9999
R
40504
LED Status
individual bits
are 0 or 1
R
Bits indicate status of LED’s:
b0 = RUN
b1 = OFF
b2 = AUTO
b3 = ALARM
b4 = LOAD
b5 = NOT IN AUTO
40507
Read Relay Image of both Main
and Aux Output
(Duplicate of 40298)
individual bits
are 0 or 1
R
Main is in lower byte and Aux is in
upper byte.
b0 = Aux Output 1,
b1 = Aux Output 2,
b2 = Aux Output 3,
b3 = Aux Output 4,
b4 = Aux Output 5,
b5 = Aux Output 6,
b6 = Aux Output 7,
b7 = Aux Output 8.
b8 = Master Start Relay,
b9 = Fuel Solenoid Relay,
b10 = PreHeat PreLube Relay,
b11 = Alarm Relay,
b12 = UNASSIGNED,
b13 = Buzzer On,
b14 = EPS Loaded Relay,
b15 = PreAlarm Relay,
40508
Input Contacts States
(Duplicate of 40273)
individual bits
are 0 or 1
R
b0 = coolant level,
b1 = ATS,
b2 = E-stop,
b3 = charger failed,
b4 = aux. input 1,
b5 = aux. input 2,
b6 = aux. input 3,
b7 = aux. input 4.
/* b7 =
aux. input 4. */
40509-604
RESERVED
OVERCURRENT
40605
51 Pick-up – 3-phase
18-118,
90-775
R W
0.18-1.18 Aac for 1A CTs,
0.90-7.75 Aac for 5A CTs