Basler Electric DGC-2020 User Manual
Page 492

B-60
DGC-2020 Modbus
™ Communication
9400200990 Rev X
Register
Description
Type
Units
Scaling
Factor
R/W
Range
45538-39
AEM Input Threshold
Status Bits Reg 2
Uint32
N/A
N/A
R
Bit 0 = Not Used
Bit 1 = Not Used
Bit 2 = RTD Input 4 Under 2
Bit 3 = RTD Input 4 Under 1
Bit 4 = RTD Input 4 Over 2
Bit 5 = RTD Input 4 Over 1
Bit 6 = RTD Input 4 Out of Range
Bit 7 = RTD Input 3 Under 2
Bit 8 = RTD Input 3 Under 1
Bit 9 = RTD Input 3 Over 2
Bit 10 = RTD Input 3 Over 1
Bit 11 = RTD Input 3 Out of Range
Bit 12 = RTD Input 2 Under 2
Bit 13 = RTD Input 2 Under 1
Bit 14 = RTD Input 2 Over 2
Bit 15 = RTD Input 2 Over 1
Bit 16 = RTD Input 2 Out of Range
Bit 17 = RTD Input 1 Under 2
Bit 18 = RTD Input 1 Under 1
Bit 19 = RTD Input 1 Over 2
Bit 20 = RTD Input 1 Over 1
Bit 21 = RTD Input 1 Out of Range
Bit 22 = Analog Input 8 Under 2
Bit 23 = Analog Input 8 Under 1
Bit 24 = Analog Input 8 Over 2
Bit 25 = Analog Input 8 Over 1
Bit 26 = Analog Input 8 Out of
Range
Bit 27 = Analog Input 7 Under 2
Bit 28 = Analog Input 7 Under 1
Bit 29 = Analog Input 7 Over 2
Bit 30 = Analog Input 7 Over 1
Bit 31 = Analog Input 7 Out of
Range