Mains Fail Transfer Status
The Mains Fail Transfer Status screen displays the Mains Fail Transfer State and any timers relevant to
the mains fail transfer process. These parameters are listed below.
Mains Fail Transfer State: The different mains fail transfer states are described below.
Power From Mains: Power is being supplied to the load from the mains bus.
Transfer Time Active: Transfer Delay timer is actively counting.
Transferring to Gens: Load is being transferred to the generator bus.
Power From Gens: Power is being supplied to the load from the generator bus.
Return Timer Active: Return Delay timer is actively counting.
Transferring to Mains: Load is being transferred to the mains bus.
Disabled: DGC-2020 is in the OFF or RUN operating mode or in the alarm state.
Remaining Transfer Delay: Displays the current timer value in seconds.
Remaining Return Delay: Displays the current timer value in seconds.
Remaining Max Parallel Time: Displays the current timer value in seconds.
Remaining Max Transfer Time: Displays the current timer value in seconds.
Remaining Open Transition Delay Time: Displays the current timer value in seconds.
Figure 4-117. Metering, Mains Fail Transfer Status