9400200990 Rev X

DGC-2020 Modbus

™ Communication

B-123

Holding

Register

Parameter

Range

Read/Write

Supported

Data

Format

Units

SYSTEM PARAMETERS

40023

Default Generator Connection

0-2

R W

0=3ph L-L
1=3ph L-N
2=1ph A-B

40024

NFPA Level

0-2

R W

0=Off
1=Level 1
2=Level 2

40025

RESERVED

40026

Rated Engine RPM

750-3600

R W

RPM

40027

Number Flywheel Teeth

50-500

R W

40028

Genset kW Rating

25-9999

R W

KWatt

40029

No Load Cool Down Time

0-60

R W

Minutes

GENERATOR PT PRIMARY

40030

Voltage(a)

1-15000

R W

DP

VoltsAC x10000

40031

Voltage(b)

R W

DP

VoltsAC

GENERATOR PT SECONDARY

40032

Voltage

1-480

R W

VoltsAC

GENERATOR CT PRIMARY

40033

Current

1-5000

R W

AmpsAC

LOW FUEL ALARM

40034

Enable

0-1

R W

0 =Off
1 =On

40035

Threshold

2-50

R W

% Full Tank

LOW FUEL PRE-ALARM

40036

Enable

0-1

R W

0 =Off
1 =On

40037

Threshold

10-100

R W

% Full Tank

LOW COOLANT TEMP PRE-ALARM

40038

Enable

0-1

R W

0 =Off
1 =On

40039

Threshold

32-150

R W

Degrees F

BATTERY OVERVOLTAGE PRE-ALARM

40040

Enable

0-1

R W

0 =Off
1 =On

40041

RESERVED

MAINTENANCE INTERVAL PRE-ALARM

40042

Enable

0-1

R W

0 =Off
1 =On

40043

Threshold

0-5000

R W

Hours

ENGINE KW OVERLOAD PRE-ALARM

40044

Enable

0-1

R W

0 =Off
1 =On

40045

Threshold

95-140

R W

% of Rated

HIGH COOLANT TEMP PRE-ALARM

40046

Enable

0-1

R W

0 =Off
1 =On

40047

Threshold

100-280

R W

Degrees F

LOW OIL PRESSURE PRE-ALARM

40048

Enable

0-1

R W

0 =Off
1 =On

40049

Threshold

3-100

R W

PSI

LOW BATTERY VOLTAGE PRE-ALARM

40050

Enable

0-1

R W

0 =Off
1 =On

40051

Threshold

60-120 (12V)
120-240 (24V)

R W

0.1 Volts DC

40052

Pre-alarm Activation Time Delay

1-10

R W

Seconds

WEAK BATTERY VOLTAGE PRE-ALARM

40053

Enable

0-1

R W

0 =Off
1 =On