DGC-2020 Modbus
™ Communication
B-123
Holding
Register
Parameter
Range
Read/Write
Supported
Data
Format
Units
SYSTEM PARAMETERS
40023
Default Generator Connection
0-2
R W
0=3ph L-L
1=3ph L-N
2=1ph A-B
40024
NFPA Level
0-2
R W
0=Off
1=Level 1
2=Level 2
40025
RESERVED
40026
Rated Engine RPM
750-3600
R W
RPM
40027
Number Flywheel Teeth
50-500
R W
40028
Genset kW Rating
25-9999
R W
KWatt
40029
No Load Cool Down Time
0-60
R W
Minutes
GENERATOR PT PRIMARY
40030
Voltage(a)
1-15000
R W
DP
VoltsAC x10000
40031
Voltage(b)
R W
DP
VoltsAC
GENERATOR PT SECONDARY
40032
Voltage
1-480
R W
VoltsAC
GENERATOR CT PRIMARY
40033
Current
1-5000
R W
AmpsAC
LOW FUEL ALARM
40034
Enable
0-1
R W
0 =Off
1 =On
40035
Threshold
2-50
R W
% Full Tank
LOW FUEL PRE-ALARM
40036
Enable
0-1
R W
0 =Off
1 =On
40037
Threshold
10-100
R W
% Full Tank
LOW COOLANT TEMP PRE-ALARM
40038
Enable
0-1
R W
0 =Off
1 =On
40039
Threshold
32-150
R W
Degrees F
BATTERY OVERVOLTAGE PRE-ALARM
40040
Enable
0-1
R W
0 =Off
1 =On
40041
RESERVED
MAINTENANCE INTERVAL PRE-ALARM
40042
Enable
0-1
R W
0 =Off
1 =On
40043
Threshold
0-5000
R W
Hours
ENGINE KW OVERLOAD PRE-ALARM
40044
Enable
0-1
R W
0 =Off
1 =On
40045
Threshold
95-140
R W
% of Rated
HIGH COOLANT TEMP PRE-ALARM
40046
Enable
0-1
R W
0 =Off
1 =On
40047
Threshold
100-280
R W
Degrees F
LOW OIL PRESSURE PRE-ALARM
40048
Enable
0-1
R W
0 =Off
1 =On
40049
Threshold
3-100
R W
PSI
LOW BATTERY VOLTAGE PRE-ALARM
40050
Enable
0-1
R W
0 =Off
1 =On
40051
Threshold
60-120 (12V)
120-240 (24V)
R W
0.1 Volts DC
40052
Pre-alarm Activation Time Delay
1-10
R W
Seconds
WEAK BATTERY VOLTAGE PRE-ALARM
40053
Enable
0-1
R W
0 =Off
1 =On