Gen breaker open, Gen breaker close, Mains breaker open – Basler Electric DGC-2020 User Manual
Page 455: Mains breaker close, Future use, Virtual input 1 close, Virtual input 1 open, Virtual input 2 close, Virtual input 2 open, Virtual input 3 close
9400200990 Rev X
DGC-2020 Modbus
™ Communication
B-23
Register
Description
Type
Units
Scaling Factor
R/W
Range
43764
Gen Breaker Open
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
43766
Gen Breaker Close
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
43768
Mains Breaker Open
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
43770
Mains Breaker Close
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
43772
FUTURE USE
43774
Virtual Input 1 Close
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
43776
Virtual Input 1 Open
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
43778
Virtual Input 2 Close
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
43780
Virtual Input 2 Open
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
43782
Virtual Input 3 Close
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
43784
Virtual Input 3 Open
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
43786
Virtual Input 4 Close
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
43788
Virtual Input 4 Open
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
43790
ESTOP Latch Status
Int32
N/A
N/A
R
0 = Disabled
1 = Enabled
43792
Gen Breaker Open
Int32
N/A
N/A
RW
1 = Operate (non-latching)
43794
Gen Breaker Close
Int32
N/A
N/A
RW
1 = Operate (non-latching)
43796
Mains Breaker Open
Int32
N/A
N/A
RW
1 = Operate (non-latching)
43798
Mains Breaker Close
Int32
N/A
N/A
RW
1 = Operate (non-latching)
43800-4006
FUTURE USE
Communication
Register
Description
Type
Units
Scaling
Factor
R/W
Range
44008
RESERVED
44010-16
FUTURE USE
44018
Modem Inter Dialout Activation
Delay
Int32
Second
N/A
RW
0 = 15
1 = 30
2 = 60
3 = 120
44020
Modem Pager Buffer Limit
Int32
N/A
N/A
RW
0 = 80 Chars
1 = 120 Chars
2 = 160 Chars
3 = 200 Chars
44022
Modem Pager Coms Data
Format
Int32
N/A
N/A
RW
0 = 8 bit, no parity
1 = 7 bit, even parity