Basler Electric DGC-2020 User Manual
Page 551

9400200990 Rev X
DGC-2020 Modbus
™ Communication
B-119
Register
Description
Type
Units
Scaling
Factor
R/W
Range
47094
AEM1 RTD4 Over1
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
47096
AEM1 RTD4 Over2
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
47098
AEM1 RTD4 Under1
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
47100
AEM1 RTD4 Under2
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
47102
AEM1 RTD4 Out of
Range Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
47104
AEM1 RTD5 Hysteresis
Int32
DeciPercent
Deci
RW
0 - 1000
47106
AEM1 RTD5 Arming
Delay
Int32
Second
N/A
RW
0 - 300
47108
AEM1 RTD5 Threshold1
Activation Delay
Int32
Second
N/A
RW
0 - 300
47110
AEM1 RTD5 Threshold2
Activation Delay
Int32
Second
N/A
RW
0 - 2
47112
AEM1 RTD5 Over1
Threshold
Int32
Deg F
N/A
RW
-58 - 482
47114
AEM1 RTD5 Over2
Threshold
Int32
Deg F
N/A
RW
-58 - 482
47116
AEM1 RTD5 Under1
Threshold
Int32
Deg F
N/A
RW
-58 - 482
47118
AEM1 RTD5 Under2
Threshold
Int32
Deg F
N/A
RW
-58 - 482
47120
AEM1 RTD5 Over1
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
47122
AEM1 RTD5 Over2
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
47124
AEM1 RTD5 Under1
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
47126
AEM1 RTD5 Under2
Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
47128
AEM1 RTD5 Out of
Range Alarm Type
Int32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only
47130
AEM1 RTD6 Hysteresis
Int32
DeciPercent
Deci
RW
0 - 1000
47132
AEM1 RTD6 Arming
Delay
Int32
Second
N/A
RW
0 - 300
47134
AEM1 RTD6 Threshold1
Activation Delay
Int32
Second
N/A
RW
0 - 300
47136
AEM1 RTD6 Threshold2
Activation Delay
Int32
Second
N/A
RW
0 - 2
47138
AEM1 RTD6 Over1
Threshold
Int32
Deg F
N/A
RW
-58 - 482