DGC-2020 Modbus

™ Communication

B-119

Register

Description

Type

Units

Scaling

Factor

R/W

Range

47094

AEM1 RTD4 Over1
Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only

47096

AEM1 RTD4 Over2
Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only

47098

AEM1 RTD4 Under1
Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only

47100

AEM1 RTD4 Under2
Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only

47102

AEM1 RTD4 Out of
Range Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only

47104

AEM1 RTD5 Hysteresis

Int32

DeciPercent

Deci

RW

0 - 1000

47106

AEM1 RTD5 Arming
Delay

Int32

Second

N/A

RW

0 - 300

47108

AEM1 RTD5 Threshold1
Activation Delay

Int32

Second

N/A

RW

0 - 300

47110

AEM1 RTD5 Threshold2
Activation Delay

Int32

Second

N/A

RW

0 - 2

47112

AEM1 RTD5 Over1
Threshold

Int32

Deg F

N/A

RW

-58 - 482

47114

AEM1 RTD5 Over2
Threshold

Int32

Deg F

N/A

RW

-58 - 482

47116

AEM1 RTD5 Under1
Threshold

Int32

Deg F

N/A

RW

-58 - 482

47118

AEM1 RTD5 Under2
Threshold

Int32

Deg F

N/A

RW

-58 - 482

47120

AEM1 RTD5 Over1
Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only

47122

AEM1 RTD5 Over2
Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only

47124

AEM1 RTD5 Under1
Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only

47126

AEM1 RTD5 Under2
Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only

47128

AEM1 RTD5 Out of
Range Alarm Type

Int32

N/A

N/A

RW

0 = None
1 = Alarm
2 = Pre-alarm
3 = Status Only

47130

AEM1 RTD6 Hysteresis

Int32

DeciPercent

Deci

RW

0 - 1000

47132

AEM1 RTD6 Arming
Delay

Int32

Second

N/A

RW

0 - 300

47134

AEM1 RTD6 Threshold1
Activation Delay

Int32

Second

N/A

RW

0 - 300

47136

AEM1 RTD6 Threshold2
Activation Delay

Int32

Second

N/A

RW

0 - 2

47138

AEM1 RTD6 Over1
Threshold

Int32

Deg F

N/A

RW

-58 - 482