beautypg.com

Remote lsm inputs, Remote contact inputs, Remote lsm inputs -43 – Basler Electric DGC-2020 User Manual

Page 153: Remote contact inputs -43, Figure 4-36. remote lsm inputs -43

background image

Remote LSM Inputs

An optional LSM-2020 (Load Share Module) provides one configurable

A

analog input that can be used as

a setpoint source for var, PF, or kW control. Settings are provided for min and max input voltage

B

, and

min and max input current

C

. Refer to Bias Control Settings in this section for information selecting the

LSM-2020 input as a setpoint source.

The remote LSM inputs are incorporated into a BESTlogicPlus programmable logic scheme by selecting
them from the I/O group in BESTlogicPlus. For more details, refer to Section 5, BESTlogicPlus
Programmable Logic
.

The BESTCOMSPlus Remote LSM Inputs screen is illustrated in Figure 4-37.

Figure 4-36. Remote LSM Inputs

A

Input Type: Voltage or Current.

B

Min/Max Input Voltage: Adjustable from 0 to 10 V in 0.1 V increments.

C

Min/Max Input Current: Adjustable from 4 to 20 mA in 0.1 mA increments.

Remote Contact Inputs

An optional CEM-2020 (Contact Expansion Module) provides 10 contact inputs. Each of the 10 contact
inputs can be independently configured to annunciate an alarm or pre-alarm

A

when the input senses a

contact closure. A user-adjustable time delay

B

can be set to delay recognition of a contact input. By

default, all inputs are configured so that they do not trigger an alarm or pre-alarm.

To make identifying the contact inputs easier, a user-assigned name

C

can be given to each input.

Contacts can be recognized

D

always or only while the engine is running.

The remote contact inputs are incorporated into a BESTlogicPlus programmable logic scheme by
selecting them from the I/O group in BESTlogicPlus. For more details, refer to Section 5, BESTlogicPlus
Programmable Logic
.

Remote contact input status is available in BESTlogicPlus Programmable Logic when “None” is selected
for Alarm Configuration.

The BESTCOMSPlus Remote Contact Inputs screen is illustrated in Figure 4-37.

9400200990 Rev X

DGC-2020 BESTCOMSPlus

® Software

4-43