Alarms, High coolant temp alarm enable, High coolant temp alarm threshold – Basler Electric DGC-2020 User Manual
Page 464: Metric high coolant temp alarm threshold, High coolant temp alarm activation delay, Low oil press. alarm enable, Low oil press. alarm threshold, Metric low oil press. alarm threshold, Low oil press. alarm arming delay, Overspeed alarm enable

B-32
DGC-2020 Modbus
™ Communication
9400200990 Rev X
Register
Description
Type
Units
Scaling
Factor
R/W
Range
44480
51-3 Curve Constant N
Float
N/A
N/A
RW
0.5 - 2.5
44482
51-3 Curve Constant R
Float
N/A
N/A
RW
0 - 30
44484
78 Vector Shift Alarm Config
Uint32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
44486
78 Vector Shift Pickup
Int32
Degree
N/A
RW
2 - 90
44488
78 Open Mains Breaker on Trip
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
44490
81 ROCOF Alarm Config
Uint32
N/A
N/A
RW
0 = None
1 = Alarm
2 = Pre-Alarm
3 = Status Only
44492
81 ROCOF Pickup
Uint32
Hz/Second
Deci
RW
2 - 100
44494
81 ROCOF Activation Delay
Uint32
Second
Milli
RW
0 - 10000
44496
81 ROCOF Open Mains Breaker
on Trip
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
44498
Alternate Frequency Scale
Factor
Float
N/A
N/A
RW
0.001 - 100
Alarms
Register
Description
Type
Units
Scaling Factor
R/W
Range
44500
High Coolant Temp Alarm
Enable
Uint32
N/A
N/A
RW
0 = Disable
1 = Enable
44502
High Coolant Temp Alarm
Threshold
Uint32
Deg F
N/A
RW
100 - 280
44504
Metric High Coolant Temp Alarm
Threshold
Int32
Deg C
N/A
RW
38 - 138
44506
High Coolant Temp Alarm
Activation Delay
Uint32
Second
N/A
RW
0 - 150
44508
Low Oil Press. Alarm Enable
Uint32
N/A
N/A
RW
0 = Disable
1 = Enable
44510
Low Oil Press. Alarm Threshold
Uint32
PSI
Deci
RW
29 - 1500
44512
Metric Low Oil Press. Alarm
Threshold
Uint32
kPa
Deci
RW
200 - 10345
44514
Low Oil Press. Alarm Arming
Delay
Uint32
Second
N/A
RW
5 - 60
44516
Overspeed Alarm Enable
Uint32
N/A
N/A
RW
0 = Disable
1 = Enable
44518
Overspeed Alarm Threshold
Uint32
Percent
N/A
RW
105 - 140
44520
Overspeed Alarm Activation
Delay
Uint32
Millisecond
Milli
RW
0 - 500
44522
Low Fuel Level Alarm Enable
Uint32
N/A
N/A
RW
0 = Disable
1 = Enable
44524
Low Fuel Level Alarm Threshold
Uint32
Percent
N/A
RW
0 - 100
44526
Low Fuel Level Alarm Activation
Delay
Int32
Second
N/A
RW
0 - 30
44528
High Coolant Temp Pre-Alarm
Enable
Uint32
N/A
N/A
RW
0 = Disable
1 = Enable
44530
High Coolant Temp Pre-Alarm
Threshold
Uint32
Deg F
N/A
RW
100 - 280
44532
Metric High Coolant Temp Pre-
Alarm Threshold
Int32
Deg C
N/A
RW
38 - 138
44534
Low Coolant Temp Pre-Alarm
Enable
Uint32
N/A
N/A
RW
0 = Disable
1 = Enable
44536
Low Coolant Temp Pre-Alarm
Threshold
Uint32
Deg F
N/A
RW
35 - 151
44538
Metric Low Coolant Temp Pre-
Alarm Threshold
Int32
Deg C
N/A
RW
2 - 66
44540
High Fuel Level Pre-Alarm
Threshold
Int32
Percent
N/A
RW
0 - 150
44542
High Fuel Level Pre-Alarm
Enable
Int32
N/A
N/A
RW
0 = Disable
1 = Enable