High fuel level pre-alarm activation delay, Low fuel level pre-alarm enable, Low fuel level pre-alarm threshold – Basler Electric DGC-2020 User Manual
Page 465: Low battery pre-alarm enable, Low battery pre-alarm threshold, Low battery pre-alarm activation delay, Weak battery pre-alarm enable, Weak battery pre-alarm threshold, Weak battery pre-alarm activation delay, Battery overvoltage pre-alarm enable

9400200990 Rev X
DGC-2020 Modbus
™ Communication
B-33
Register
Description
Type
Units
Scaling Factor
R/W
Range
44544
High Fuel Level Pre-Alarm
Activation Delay
Int32
Second
N/A
RW
0 - 30
44546
Low Fuel Level Pre-Alarm
Enable
Uint32
N/A
N/A
RW
0 = Disable
1 = Enable
44548
Low Fuel Level Pre-Alarm
Threshold
Uint32
Percent
N/A
RW
10 - 100
44550
Low Battery Pre-Alarm Enable
Uint32
N/A
N/A
RW
0 = Disable
1 = Enable
44552
Low Battery Pre-Alarm
Threshold
Uint32
DeciVolt
Deci
RW
60 - 280
44554
Low Battery Pre-Alarm
Activation Delay
Uint32
Second
N/A
RW
1 - 60
44556
Weak Battery Pre-Alarm Enable
Uint32
N/A
N/A
RW
0 = Disable
1 = Enable
44558
Weak Battery Pre-Alarm
Threshold
Uint32
DeciVolt
Deci
RW
40 - 280
44560
Weak Battery Pre-Alarm
Activation Delay
Uint32
Second
Deci
RW
0 - 100
44562
Battery Overvoltage Pre-Alarm
Enable
Uint32
N/A
N/A
RW
0 = Disable
1 = Enable
44564
Low Oil Press. Pre-Alarm
Enable
Uint32
N/A
N/A
RW
0 = Disable
1 = Enable
44566
Low Oil Press. Pre-Alarm
Threshold
Uint32
PSI
Deci
RW
29 - 1500
44568
Metric Low Oil Press. Pre-Alarm
Threshold
Int32
kPa
Deci
RW
20 - 10345
44570
Engine Overload 1 Pre-Alarm
Enable
Uint32
N/A
N/A
RW
0 = Disable
1 = Enable
44572
Engine Overload 1 Pre-Alarm
Threshold
Int32
Percent
N/A
RW
0 - 200
44574
ECU Comms Fail Pre-Alarm
Enable
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
44576
Active DTC Pre-Alarm Enable
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
44578
Maintenance Interval Pre-Alarm
Enable
Uint32
N/A
N/A
RW
0 = Disable
1 = Enable
44580
Maintenance Interval Pre-Alarm
Threshold
Uint32
Hour
N/A
RW
0 - 5000
44582
Speed Sender Fail Activation
Delay
Int32
Second
N/A
RW
0 - 300
44584
ECU Low Coolant Level Alarm
Enable
Uint32
N/A
N/A
RW
0 = Disable
1 = Enable
44586
ECU Low Coolant Level Alarm
Threshold
Uint32
Percent
N/A
RW
1 - 99
44588
ECU Low Coolant Level Pre-
Alarm Enable
Uint32
N/A
N/A
RW
0 = Disable
1 = Enable
44590
ECU Low Coolant Level Pre-
Alarm Threshold
Uint32
Percent
N/A
RW
1 - 99
44592
Battery Overvoltage Alarm
Threshold
Int32
DeciVolt
Deci
RW
120 - 320
44594
Engine Overload 1 Pre-Alarm
3 Phase Hysteresis
Int32
DeciVolt
Deci
RW
1 - 10
44596
Engine Overload 1 Pre-Alarm
1 Phase Threshold
Int32
Percent
N/A
RW
0 - 200
44598
Engine Overload 1 Pre-Alarm
1 Phase Hysteresis
Int32
Percent
N/A
RW
1 - 10
44600
Engine Overload 1 Pre-Alarm
1 Phase Low Line Scale Factor
Float
N/A
N/A
RW
0.001 - 3
44602
Engine Overload 2 Pre-Alarm
Enable
Int32
N/A
N/A
RW
0 = Disable
1 = Enable
44604
Engine Overload 2 Pre-Alarm
3 Phase Threshold
Int32
Percent
N/A
RW
0 - 200
44606
Engine Overload 2 Pre-Alarm
3 Phase Hysteresis
Int32
Percent
N/A
RW