beautypg.com

High fuel level pre-alarm activation delay, Low fuel level pre-alarm enable, Low fuel level pre-alarm threshold – Basler Electric DGC-2020 User Manual

Page 465: Low battery pre-alarm enable, Low battery pre-alarm threshold, Low battery pre-alarm activation delay, Weak battery pre-alarm enable, Weak battery pre-alarm threshold, Weak battery pre-alarm activation delay, Battery overvoltage pre-alarm enable

background image

9400200990 Rev X

DGC-2020 Modbus

™ Communication

B-33

Register

Description

Type

Units

Scaling Factor

R/W

Range

44544

High Fuel Level Pre-Alarm
Activation Delay

Int32

Second

N/A

RW

0 - 30

44546

Low Fuel Level Pre-Alarm
Enable

Uint32

N/A

N/A

RW

0 = Disable
1 = Enable

44548

Low Fuel Level Pre-Alarm
Threshold

Uint32

Percent

N/A

RW

10 - 100

44550

Low Battery Pre-Alarm Enable

Uint32

N/A

N/A

RW

0 = Disable
1 = Enable

44552

Low Battery Pre-Alarm
Threshold

Uint32

DeciVolt

Deci

RW

60 - 280

44554

Low Battery Pre-Alarm
Activation Delay

Uint32

Second

N/A

RW

1 - 60

44556

Weak Battery Pre-Alarm Enable

Uint32

N/A

N/A

RW

0 = Disable
1 = Enable

44558

Weak Battery Pre-Alarm
Threshold

Uint32

DeciVolt

Deci

RW

40 - 280

44560

Weak Battery Pre-Alarm
Activation Delay

Uint32

Second

Deci

RW

0 - 100

44562

Battery Overvoltage Pre-Alarm
Enable

Uint32

N/A

N/A

RW

0 = Disable
1 = Enable

44564

Low Oil Press. Pre-Alarm
Enable

Uint32

N/A

N/A

RW

0 = Disable
1 = Enable

44566

Low Oil Press. Pre-Alarm
Threshold

Uint32

PSI

Deci

RW

29 - 1500

44568

Metric Low Oil Press. Pre-Alarm
Threshold

Int32

kPa

Deci

RW

20 - 10345

44570

Engine Overload 1 Pre-Alarm
Enable

Uint32

N/A

N/A

RW

0 = Disable
1 = Enable

44572

Engine Overload 1 Pre-Alarm
Threshold

Int32

Percent

N/A

RW

0 - 200

44574

ECU Comms Fail Pre-Alarm
Enable

Int32

N/A

N/A

RW

0 = Disable
1 = Enable

44576

Active DTC Pre-Alarm Enable

Int32

N/A

N/A

RW

0 = Disable
1 = Enable

44578

Maintenance Interval Pre-Alarm
Enable

Uint32

N/A

N/A

RW

0 = Disable
1 = Enable

44580

Maintenance Interval Pre-Alarm
Threshold

Uint32

Hour

N/A

RW

0 - 5000

44582

Speed Sender Fail Activation
Delay

Int32

Second

N/A

RW

0 - 300

44584

ECU Low Coolant Level Alarm
Enable

Uint32

N/A

N/A

RW

0 = Disable
1 = Enable

44586

ECU Low Coolant Level Alarm
Threshold

Uint32

Percent

N/A

RW

1 - 99

44588

ECU Low Coolant Level Pre-
Alarm Enable

Uint32

N/A

N/A

RW

0 = Disable
1 = Enable

44590

ECU Low Coolant Level Pre-
Alarm Threshold

Uint32

Percent

N/A

RW

1 - 99

44592

Battery Overvoltage Alarm
Threshold

Int32

DeciVolt

Deci

RW

120 - 320

44594

Engine Overload 1 Pre-Alarm
3 Phase Hysteresis

Int32

DeciVolt

Deci

RW

1 - 10

44596

Engine Overload 1 Pre-Alarm
1 Phase Threshold

Int32

Percent

N/A

RW

0 - 200

44598

Engine Overload 1 Pre-Alarm
1 Phase Hysteresis

Int32

Percent

N/A

RW

1 - 10

44600

Engine Overload 1 Pre-Alarm
1 Phase Low Line Scale Factor

Float

N/A

N/A

RW

0.001 - 3

44602

Engine Overload 2 Pre-Alarm
Enable

Int32

N/A

N/A

RW

0 = Disable
1 = Enable

44604

Engine Overload 2 Pre-Alarm
3 Phase Threshold

Int32

Percent

N/A

RW

0 - 200

44606

Engine Overload 2 Pre-Alarm
3 Phase Hysteresis

Int32

Percent

N/A

RW

1 - 10

This manual is related to the following products: