B-144

DGC-2020 Modbus

™ Communication

9400200990 Rev X

Holding

Register

Parameter

Range

Read/Write

Supported

Data

Format

Units

40451

Generator Speed Mode

Individual Bits are 0 or 1

R W

Active Speed

Signals

b0=mag pick-up
b1=generator
b2=chg. alt.

Gen. Phase Rotation
b4=0 for A-B-C
b4=1 for A-C-B

Maintenance Timer

b5=0 is active
b5=1 to reset


GENERATOR PT PRIMARY

40452

Voltage(a)

1-15000

R W

DP

VoltsAC x 10000

40453

Voltage(b)

R W

DP

VoltsAC


GENERATOR PT SECONDARY

40454

Voltage

1-480

R W

VoltsAC


GENERATOR CT PRIMARY

40455

Current

1-5000

R W

AmpsAC

40456


BUS PT PRIMARY

40457

Voltage(a)

1-15000

R W

DP

VoltsAC x 10000

40458

Voltage(b)

R W

DP

VoltsAC


BUS PT SECONDARY

40459

Voltage

1-480

R W

VoltsAC


LOW FUEL PRE-ALARM

40460

Enable

0-1

R W

0 =Off
1 =On

40461

Threshold

10-100

R W

% Full Tank


LOW COOL TEMP PRE-ALARM

40462

Enable

0-1

R W

0 =Off
1 =On

40463

Threshold

40-100

R W

DegF


BATTERY OVERVOLTAGE PRE-ALARM

40464

Enable

0-1

R W

0 =Off
1 =On

40465

Threshold

140-160 (12V)

240-320 (24V)

R W

.1 VoltDC


MAINTENANCE INTERVAL PRE-ALARM

40466

Enable

0-1

R W

0 =Off
1 =On

40467

Threshold

0-5000

R W

Hours


ENGINE KW OVERLOAD PRE-ALARM

40468

Enable

0-1

R W

0 =Off
1 =On

40469

Threshold

95-140

R W

% of Rated


HIGH COOLANT TEMPERATURE PRE-ALARM

40470

Enable

0-1

R W

0 =Off
1 =On

40471

Threshold

100-280

R W

DegF


LOW OIL PRESSURE PRE-ALARM