BESTlogic

Plus Composition

There are three main groups of objects used for programming BESTlogicPlus. These groups are I/O,
Components,
and Elements. For details on how these objects are used to program BESTlogicPlus, see
the paragraphs on Programming BESTlogicPlus.

I/O

This group contains Input Objects, Output Objects, Alarms, Pre-Alarms, Senders, and Logic Control
Relays. Table 5-1 lists the names and descriptions of the objects in the I/O group.

Table 5-1. I/O Group, Names and Descriptions

Name

Description

Symbol

Input Objects

Logic 0

Always false (Low).

Logic 1

Always true (High).

Physical Inputs

IN1 - IN16

True when Physical Input x is active.

Remote Inputs

IN17 - IN26

True when Remote Input x is active. (Available when
an optional CEM-2020 is connected.)

Virtual Inputs

VIN1 - VIN4

True when Virtual Input x is active.

Status Input

Alarm Silence

True when the Alarm Silence logic element is true or
the Alarm Silence button is pressed on the front
panel.

Status Input

Alternate
Frequency
Override

True when the Alternate Frequency Override logic
element is true.

Status Input

Analog
Expansion
Module

Analog Expansion Module Connected. True when an
optional AEM-2020 is connected to the DGC-2020.

Analog
Expansion
Module

Remote Analog
Inputs 1-8

True when Over 1, Over 2, Under 1, Under 2, or Out
of Range is configured as Status Only and the
threshold has been exceeded. (Over 1 shown.)

Analog
Expansion
Module

Remote Analog
Outputs 1-4

True when the analog output connection is open and
the Out of Range Alarm Configuration is set to Status
Only.

Analog
Expansion
Module

Remote RTD
Inputs 1-8

True when Over 1, Over 2, Under 1, Under 2, or Out
of Range is configured as Status Only and the
threshold has been exceeded. (Over 1 shown.)

Analog
Expansion
Module

Remote
Thermocouple
Inputs 1-2

True when Over 1, Over 2, Under 1, Under 2, or Out
of Range is configured as Status Only and the
threshold has been exceeded. (Over 1 shown.)

5-2

DGC-2020 BESTlogic

Plus Programmable Logic

9400200990 Rev X