Basler Electric DGC-2020 User Manual
Page 234
![background image](https://www.manualsdir.com/files/773941/content/doc234.png)
Name
Description
Symbol
Status Input
Generator
Protection
True when the 51-3 element is tripped.
Status Input
Generator
Protection
True when the 78 element is tripped.
Status Input
Generator
Protection
True when the 81 ROCOF element is tripped.
Status Input
Generator
Protection
True when the 81 Over element is tripped.
Status Input
Generator
Protection
True when the 81 Under element is tripped.
Status Input
Generator Test
Loaded
True when the Exercise Timer has started the
generator and run with load is selected.
Status Input
Generator Test
True when the Exercise Timer has started the
generator.
Status Input
Global Low
Coolant Level
True when the Low Coolant Level input is true.
Status Input
Ground Delta
Override
True when the Grounded Delta Override input is true.
Status Input
Idle Request
True when the Idle Request logic element is true.
Status Input
In Alarm State
True when the DGC-2020 is in the alarm state.
Status Input
In Connecting
State
True when the DGC-2020 is in the connecting state.
Status Input
In Cooling State
True when the DGC-2020 is in the cooling state.
Status Input
In Cranking State
True when the DGC-2020 is in the cranking state.
Status Input
In Disconnect
State
True when the DGC-2020 is in the disconnect state.
Status Input
In Prestart State
True when the DGC-2020 is in the pre-start state.
Status Input
In Pulsing State
True when the DGC-2020 is in the pulsing state.
Status Input
In Ready State
True when the DGC-2020 is in the ready state.
5-6
DGC-2020 BESTlogic
™
Plus Programmable Logic
9400200990 Rev X